Common use of Autoreclosure and Manual Energization Clause in Contracts

Autoreclosure and Manual Energization. 1.5.1 The Generator shall provide suitable equipment to protect its plant and equipment for any conditions on the transmission system such as reclosing, faults, and voltage unbalance. 1.5.2 Following a protection operation on a transmission line, the transmission breakers, located mainly in network switching and/or transformation stations, shall autoreclose after a certain time delay. Where the Generator is directly connected to the transmission line, or for configurations where the Generator could be damaged by autoreclosure of the line, the Generator shall provide a reliable means of disconnecting its equipment before autoreclosure. The Generator is responsible for protecting its own equipment and the Transmitter is not liable for damage to the Generator=s equipment except as stipulated in section 15 of this Agreement. The Generator may request a means of supervising the transmission autoreclosure prior to the disconnection of its equipment e.g. changes in protection logic at one or both stations to reduce the risk of such events. The criteria governing the use of reclosures are set out in the Ontario Hydro APolicies, Principles & Guidelines@ document AC-3.4.1(R1), Automatic Reclosure and Manual Energization on Bulk System Electricity Circuits@, which was in effect as of April 1, 1999. 1.5.3 A Generator=s transmission system breaker shall not autoreclose without the Transmitter=s approval. 1.5.4 Manual energization of a Transmitter=s line by a Generator=s facilities is permitted only under the Transmitter=s direction. SCHEDULE F (CONT=D) EXHIBIT F.1 TYPICAL GENERATOR PROTECTION REQUIREMENTS Station A Station B R Transmission System R HV Line R R 3ph Isolating Load Device Load Load HV Line ** 3 VTs X00 X00 XX / XX *** F HVI B21 Directioned A21 Generating Station Generator A87 Transformer B87 * 3 VTs 27,59 81U,81O F G Synchronous Generator **** NOTES: * System security may dictate two transformer differential ACCEPTABILITY OF TRANSFORMER CONFIGURATION protections. If not required, a HV backup relay (51B) is IS SITE SPECIFIC. acceptable provided satisfactory settings can be applied. ** May be included as integral part of HVI. *** RT may be duplicated at Transmitter discretion. **** Generator Protection to be specified and supplied by generator and consultant. Typical Protection - Generation Connected to Transmission System SCHEDULE F (CONT=D) OESC Transmission System HV Line X X 0 XXx X00 X00 X00 Directioned B21 F HVI Generator's Switching Station at Interface X00 Xxxxxxxxxxx X00 XX / XX *** Generator’s HV Line ** 3 VTs X00 X XXX X00 NOTES: B21 * System security may dictate two transformer differential protections. If not required, a HV backup relay (51B) is acceptable provided satisfactory settings can be applied. Directioned A21 ** May be included as integral part of HVI. A87 * B87 *** RT may be duplicated at OESC Transmission System discretion. 3 VTs **** Generator Protection to be specified and supplied by generator and his consultant. F Synchronous G Generator **** Typical Protection - Generation Connected to OESC Transmission System via Generator Owned Transmission Line 81U, 81O 27, 59 M M M SCHEDULE F (CONT=D) EXHIBIT F.3 TYPICAL GENERATOR PROTECTIONS The following are typical Generator protections. The actual ones are to be specified and supplied by the Generator and his consultants. The Transmitter will be interested in the capabilities and settings of the frequency protections and voltage protections. The settings of the frequency protections on large units must comply with NPCC performance requirements. All protections settings must be submitted to the Transmitter and the IESO.

Appears in 1 contract

Samples: Connection Agreement

AutoNDA by SimpleDocs

Autoreclosure and Manual Energization. 1.5.1 The Generator shall provide suitable equipment to protect its plant and equipment for any conditions on the transmission system such as reclosing, faults, and voltage unbalance. 1.5.2 Following a protection operation on a transmission line, the transmission breakers, located mainly in network switching and/or transformation stations, shall autoreclose after a certain time delay. Where the Generator is directly connected to the transmission line, or for configurations where the Generator could be damaged by autoreclosure of the line, the Generator shall provide a reliable means of disconnecting its equipment before autoreclosure. The Generator is responsible for protecting its own equipment and the Transmitter is not liable for damage to the Generator=s equipment except as stipulated in section 15 of this Agreement. The Generator may request a means of supervising the transmission autoreclosure prior to the disconnection of its equipment e.g. changes in protection logic at one or both stations to reduce the risk of such events. The criteria governing the use of reclosures are set out in the Ontario Hydro APolicies, Principles & Guidelines@ document AC-3.4.1(R1), Automatic Reclosure and Manual Energization on Bulk System Electricity Circuits@, which was in effect as of April 1, 1999. 1.5.3 A Generator=s transmission system breaker shall not autoreclose without the Transmitter=s approval.. Transmission System Code, Appendix 1 (version B) 1.5.4 Manual energization of a Transmitter=s line by a Generator=s facilities is permitted only under the Transmitter=s direction. Transmission System Code, Appendix 1 (version B) SCHEDULE F (CONT=D) EXHIBIT F.1 TYPICAL GENERATOR PROTECTION REQUIREMENTS Station A Station B R Transmission System R HV Line R R 3ph Isolating Load Device Load Load HV Line ** 3 VTs X00 X00 XX / XX *** F HVI B21 Directioned A21 Generating Station Generator A87 Transformer B87 * 3 VTs 27,59 81U,81O F G Synchronous Generator **** NOTES: * System security may dictate two transformer differential ACCEPTABILITY OF TRANSFORMER CONFIGURATION protections. If not required, a HV backup relay (51B) is IS SITE SPECIFIC. acceptable provided satisfactory settings can be applied. ** May be included as integral part of HVI. *** RT may be duplicated at Transmitter discretion. **** Generator Protection to be specified and supplied by generator and consultant. Typical Protection - Generation Connected to Transmission System Transmission System Code, Appendix 1 (version B) SCHEDULE F (CONT=D) M M M EXHIBIT F.2 TYPICAL GENERATOR-OWNED TRANSMISSION LINE PROTECTION REQUIREMENTS Station A Station B R OESC Transmission System R HV Line X X 0 XXx X00 X00 X00 R R 3 VTs A21 A21 B21 Directioned B21 Generator's F HVI Generator's Switching Station at Interface X00 Xxxxxxxxxxx X00 XX / XX *** Generator’s HV Line ** 3 VTs X00 X XXX X00 F HVI NOTES: B21 * System security may dictate two transformer differential protections. If not required, a HV backup relay (51B) is acceptable provided B21 satisfactory settings can be applied. Directioned A21 ** May be included as integral part of HVI. A87 * B87 *** RT may be duplicated at OESC B87 Transmission System discretion. 3 VTs **** Generator Protection to be specified and 27, 59 supplied by generator and his consultant. 81U, 81O F ACCEPTABILITY OF TRANSFORMER CONFIGURATION IS SITE SPECIFIC. OESC WRITTEN APPROVAL MUST BE OBTAINED. Synchronous G Generator **** Typical Protection - Generation Connected to OESC Transmission System via Generator Owned Transmission Line 81UTransmission System Code, 81O 27, 59 M M M Appendix 1 (version B) SCHEDULE F (CONT=D) EXHIBIT F.3 TYPICAL GENERATOR PROTECTIONS The following are typical Generator protections. The actual ones are to be specified and supplied by the Generator and his consultants. The Transmitter will be interested in the capabilities and settings of the frequency protections and voltage protections. The settings of the frequency protections on large units must comply with NPCC performance requirements. All protections settings must be submitted to the Transmitter and the IESO.. Transmission System Code, Appendix 1 (version B)

Appears in 1 contract

Samples: Connection Agreement

Autoreclosure and Manual Energization. 1.5.1 The Generator shall provide suitable equipment to protect its plant and equipment for any conditions on the transmission system such as reclosing, faults, and voltage unbalance. 1.5.2 Following a protection operation on a transmission line, the transmission breakers, located mainly in network switching and/or transformation stations, shall autoreclose reclose after a certain time delay. Where the Generator is directly connected to the transmission line, or for configurations where the Generator could be damaged by autoreclosure of the line, the The Generator shall provide a reliable means of disconnecting its equipment before autoreclosurethis reclosure. The Generator is responsible for protecting its own equipment and the Transmitter is not liable for damage to the Generator=s equipment except as stipulated in section 15 of this Agreement’s equipment. The Generator may request a means of supervising the transmission autoreclosure reclosure prior to the disconnection of its equipment e.g. changes in protection logic at one or both stations to reduce the risk of such events. The criteria governing the use of reclosures are set out in the Ontario Hydro APolicies, Principles & Guidelines@ document AC-3.4.1(R1), Automatic Reclosure and Manual Energization on Bulk System Electricity Circuits@, which was in effect as of April 1, 1999. 1.5.3 A Generator=s ’s transmission system breaker shall not autoreclose without the Transmitter=s ’s approval. 1.5.4 Manual energization of a Transmitter=s ’s line by a Generator=s ’s facilities is permitted only under the Transmitter=s ’s direction. SCHEDULE F (CONT=D) EXHIBIT F.1 TYPICAL GENERATOR PROTECTION REQUIREMENTS Station A Station B R Transmission System R HV Line R R 3ph Isolating Load Device Load Load HV Line ** 3 VTs X00 X00 XX A21 B21 RT / XX TT *** F HVI B21 Directioned A21 Generating Station Generator A87 Transformer B87 * 3 VTs 27,59 81U,81O F G Synchronous Generator **** NOTES: * System security may dictate two transformer differential ACCEPTABILITY OF TRANSFORMER CONFIGURATION protections. If not required, a HV backup relay (51B) is IS SITE SPECIFIC. acceptable provided satisfactory settings can be applied. ** May be included as integral part of HVI. *** RT may be duplicated at Transmitter discretion. **** Generator Protection to be specified and supplied by generator and consultant. Typical Protection - Generation Connected to Transmission System SCHEDULE F (CONT=D) OESC Transmission System HV Line X X 0 XXx X00 X00 X00 R R 3 VTs A21 Directioned B21 F HVI Generator's Switching Station at Interface X00 Xxxxxxxxxxx X00 XX B21 Directioned A21 RT / XX TT *** Generator’s HV Line ** 3 VTs X00 X XXX X00 NOTES: B21 * System security may dictate two transformer differential protections. If not required, a HV backup relay (51B) is acceptable provided satisfactory settings can be applied. Directioned A21 ** May be included as integral part of HVI. A87 * B87 *** RT may be duplicated at OESC Transmission System discretion. 3 VTs **** Generator Protection to be specified and supplied by generator and his consultant. F Synchronous G Generator **** Typical Protection - Generation Connected to OESC Transmission System via Generator Owned Transmission Line 81U, 81O 27, 59 M M M SCHEDULE F (CONT=D) EXHIBIT F.3 TYPICAL GENERATOR PROTECTIONS The following are typical Generator protections. The actual ones are to be specified and supplied by the Generator and his consultants. The Transmitter will be interested in the capabilities and settings of the frequency protections and voltage protections. The settings of the frequency protections on large units must comply with NPCC performance requirements. All protections settings must be submitted to the Transmitter and the IESO.

Appears in 1 contract

Samples: Connection Agreement

AutoNDA by SimpleDocs

Autoreclosure and Manual Energization. 1.5.1 The Generator shall provide suitable equipment to protect its plant and equipment for any conditions on the transmission system such as reclosing, faults, and voltage unbalance. 1.5.2 Following a protection operation on a transmission line, the transmission breakers, located mainly in network switching and/or transformation stations, shall autoreclose after a certain time delay. Where the Generator is directly connected to the transmission line, or for configurations where the Generator could be damaged by autoreclosure of the line, the Generator shall provide a reliable means of disconnecting its equipment before autoreclosure. The Generator is responsible for protecting its own equipment and the Transmitter is not liable for damage to the Generator=s ’s equipment except as stipulated in section 15 of this Agreement. The Generator may request a means of supervising the transmission autoreclosure prior to the disconnection of its equipment e.g. changes in protection logic at one or both stations to reduce the risk of such events. The criteria governing the use of reclosures are set out in the Ontario Hydro APolicies“Policies, Principles & Guidelines@ Guidelines” document AC-3.4.1(R1“C-3.4.1(R1), Automatic Reclosure and Manual Energization on Bulk System Electricity Circuits@Circuits”, which was in effect as of April 1, 1999. 1.5.3 A Generator=s ’s transmission system breaker shall not autoreclose without the Transmitter=s ’s approval. 1.5.4 Manual energization of a Transmitter=s ’s line by a Generator=s ’s facilities is permitted only under the Transmitter=s ’s direction. SCHEDULE F (CONT=D) EXHIBIT F.1 TYPICAL GENERATOR PROTECTION REQUIREMENTS Station A Station B R Transmission System R HV Line R R 3ph Isolating Load Device Load Load HV Line ** 3 VTs X00 X00 XX / XX *** F HVI B21 Directioned A21 Generating Station Generator A87 Transformer B87 * 3 VTs 27,59 81U,81O F G Synchronous Generator **** NOTES: * System security may dictate two transformer differential ACCEPTABILITY OF TRANSFORMER CONFIGURATION protections. If not required, a HV backup relay (51B) is IS SITE SPECIFIC. acceptable provided satisfactory settings can be applied. ** May be included as integral part of HVI. *** RT may be duplicated at Transmitter discretion. **** Generator Protection to be specified and supplied by generator and consultant. Typical Protection - Generation Connected to Transmission System SCHEDULE F (CONT=D) OESC Transmission System HV Line X X 0 XXx X00 X00 X00 Directioned B21 F HVI Generator's Switching Station at Interface X00 Xxxxxxxxxxx X00 XX / XX *** Generator’s HV Line ** 3 VTs X00 X XXX X00 NOTES: B21 * System security may dictate two transformer differential protections. If not required, a HV backup relay (51B) is acceptable provided satisfactory settings can be applied. Directioned A21 ** May be included as integral part of HVI. A87 * B87 *** RT may be duplicated at OESC Transmission System discretion. 3 VTs **** Generator Protection to be specified and supplied by generator and his consultant. F Synchronous G Generator **** Typical Protection - Generation Connected to OESC Transmission System via Generator Owned Transmission Line 81U, 81O 27, 59 B21 M M M SCHEDULE F (CONT=D) EXHIBIT F.3 TYPICAL GENERATOR PROTECTIONS The following are typical Generator protections. The actual ones are to be specified and supplied by the Generator and his consultants. The Transmitter will be interested in the capabilities and settings of the frequency protections and voltage protections. The settings of the frequency protections on large units must comply with NPCC performance requirements. All protections settings must be submitted to the Transmitter and the IESO.

Appears in 1 contract

Samples: Connection Agreement

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!