Cable requirements. The cables shall comply with the relevant standard and bear the relevant rating such as TC-ER for the North American version. • The trunk cable conductors shall be color coded appropriately: US Black Red Blue White Green or Green/Yellow EU Xxxxx Black Grey Blue Green/Yellow • The Drop cable can optionally use the same color code as the Trunk cable. If uniform color is used, such as all black, markings shall be added to identify the conductor number • The cable shall be flexible. The minimum bend radius shall be 10 times the cable outside diameter. • The wire arrangement shall be as such: 4 conductor (future) X0 XX X0 X 3 conductor (future) — XX X0 N • Minimum wire gauges shall be 12 AWG and 18 AWG for the trunk and drop wires respectively.