Collector System Equivalent. If the generation is from a wind plant or PV solar facility, Interconnection Customer shall provide equivalent lumped positive, negative, and zero sequence impedance (R, X, B) of the UG cable and OH medium voltage (typically 34.5kV) collector system. This lumped equivalent impedance shall approximate the real and reactive losses seen by the average wind generator or PV solar facility, in a form consistent with the WECC Wind Generator Modeling Group May 2008 (or latest) modeling guide. In the course of the SIS, Transmission Provider will determine whether a more detailed model of the collector system is required.