Exterior Grounding. Ground Rods There will be driven ground rods located at each corner of the building, and at the AC service entrance and waveguide entry port. These rods will be made of copper clad high strength steel with minimum dimensions of 5/8" x 8'. The rods will be located at least 24" from the edge of the foundations, and driven such that the top of the rod is below the frost line of the installation site. The rods will be exothermically welded to the external halo drops.

Appears in 3 contracts

Samples: Fixed Point Microwave Services Agreement (Pathnet Inc), Fixed Point Microwave Services Agreement (Pathnet Inc), Fixed Point Microwave Services Agreement (Pathnet Inc)

AutoNDA by SimpleDocs

Exterior Grounding. 5.3.1. Ground Rods There will be driven ground rods located at each corner of the building, and at the AC service entrance and waveguide entry port. These rods will be made of copper clad high strength steel with minimum dimensions of 5/8" x 8'. The rods will be located at least 24" from the edge of the foundations, and driven such that the top of the rod is below the frost line of the installation site. The rods will be exothermically welded to the external halo drops.