Frequency, Power Factor and Voltage Limits Clause Samples

Frequency, Power Factor and Voltage Limits. (a) At rated voltage and frequency, the Facility will operate at 100% load with a power factor in the range 0.85 lagging to 0.95 leading at the Delivery Point, which range shall not be exceeded. (b) The Facility will operate within the line voltage range used in practice by BPDB and in no case shall the Facility be required to operate more than +10% or less than -20% on the 33 kV high voltage system. (c) The Facility shall operate within the frequency range 48.5 Hertz to 51.5 Hertz which range shall not be exceeded. The Facility shall be capable of continuous operation for the periods defined in Table 2, 48.5 to 51.5 Continuous 47.5 to 48.5 10 minutes