Inhibited Parallel Operation. If while operating parallel to SPPCo's system, or while attempting to bring the generating system on-line and operate parallel to SPPCo's system, any of the protective relays or devices operate inhibiting parallel operation, the customer will follow these procedures prior to attempting parallel operation with SPPCo again: 4.1 Determine if SPPCo's circuit is energized or de-energized by checking the status of the relays described in Section E-5.2 and/or contacting the local SPPCo office. 4.2 If it is determined that the SPPCo circuit is and has been continuously energized, then the customer will not attempt to reconnect his system parallel to SPPCo's system, until the cause of protective device operation has been corrected, and it has been determined that the customer's system is in proper operating condition. 4.3 If it is determined that the SPPCo circuit is de-energized, the customer must not attempt to reconnect his system and operate parallel with SPPCo's system until he has confirmed that power has been restored and SPPCo's circuit is energized. 4.4 The customer is not prohibited from isolating his system and supplying his own load while SPPCo's circuit is de-energized.
Appears in 2 contracts
Samples: Purchase and Sale Agreement (Brady Power Partners), Purchase and Sale Agreement (Ormat Funding Corp.)
Inhibited Parallel Operation. If while operating parallel to SPPCo's system, or while attempting to bring the generating system on-line and operate parallel to SPPCo's system, any of the protective relays or devices operate inhibiting parallel operation, the customer will follow these procedures prior to attempting parallel operation with SPPCo again:
4.1 8.4.1 Determine if SPPCo's circuit is energized or de-energized by checking the status of the relays described in Section E-5.2 and/or contacting the local SPPCo office.
4.2 8.4.2 If it is determined that the SPPCo circuit is and has been continuously energized, then the customer will not attempt to reconnect his system parallel to SPPCo's system, until the cause of protective device operation has been corrected, and it has been determined that the customer's system is in proper operating condition.
4.3 8.4.3 If it is determined that the SPPCo circuit is de-energized, the customer must not attempt to reconnect his system and operate parallel with SPPCo's system until he has confirmed that power has been restored and SPPCo's circuit is energized.
4.4 8.4.4 The customer is not prohibited from isolating his system and supplying his own load while SPPCo's circuit is de-energized.
Appears in 2 contracts
Samples: Purchase and Sale of Electricity Agreement (Brady Power Partners), Purchase and Sale Agreement (Ormat Funding Corp.)