Common use of INSTALLATION TOLERANCES Clause in Contracts

INSTALLATION TOLERANCES. 2.4.1. Air Handling Systems: Adjust to within plus or minus 10 percent of design conditions for supply systems and within plus or minus 10 percent of design conditions for return and exhaust systems. 2.4.2. Air Outlets and Inlets: Adjust total to within plus or minus 10 percent of design conditions to space. Adjust outlets and inlets in space to within plus or minus 10 percent of design conditions. 2.4.3. If tested air quantities are not within the required limits, the Contractor must replace fan pulleys, sheaves, belts, or add balancing dampers, etc. as required to meet the Specifications. If acceptable to Contractor, TAB Agency may install replacement pulleys, sheaves, or belts as required to meet the Specifications. Installation of pulleys, sheaves, or belts by TAB Agency shall have no effect on Contractor’s warranty. 2.4.4. Water: Adjust to within plus or minus 10 percent of design conditions.