Line structures Sample Clauses

Line structures. Structures will be designed for the layouts indicated in section 3.1.1. They will be of the lattice type and self-supported. The 500 kV structures shall carry not less than four conductors per phase and two (02) guy wires, one of the OPGW type and the other of the conventional type. Structures in 220 kV will have at least two conductors per phase and two (02) guy wires, one of the OPGW type and the other of the conventional type.
AutoNDA by SimpleDocs
Line structures. Structures shall be designed for the layouts indicated in section 3.1.1, of the lattice-type and self-supported. The 220 kV structures of the new line shall have at least one conductor per phase and an optical fiber cable.
Line structures. The structures will be designed for the configurations indicated in Paragraph 4.1.1.

Related to Line structures

  • Other Structures You may use up to 10% of the Coverage A limit of liability for loss by a Peril Insured Against to other structures described in Coverage B. This coverage is additional insurance.

  • BUILDINGS AND STRUCTURES 1. Repair or retrofit of buildings less than 45 years old.

  • Structures Airport facilities such as bridges; culverts; catch basins, inlets, retaining walls, cribbing; storm and sanitary sewer lines; water lines; underdrains; electrical ducts, manholes, handholes, lighting fixtures and bases; transformers; flexible and rigid pavements; navigational aids; buildings; vaults; and, other manmade features of the airport that may be encountered in the work and not otherwise classified herein. 10-50 SUBGRADE. The soil which forms the pavement foundation.

  • Exterior and interior functional areas and spaces of the Project, with technical and equipment requirements on each;

  • PRICING STRUCTURES Licenses and Support Services for the Licensed Programs to which this OST applies are granted according to the pricing structures mentioned in the related Transaction Document. Standard pricing structures are defined in the section “DEFINITIONS” of this OST, even though those pricing structures may not be applicable to the DS Offerings to which this OST applies. Other pricing structures may be made available on a case-by-case basis.

  • Line Splitting 3.7.1 Line splitting allows a provider of data services (a Data LEC) and a provider of voice services (a Voice CLEC) to deliver voice and data service to End Users over the same Loop. The Voice CLEC and Data LEC may be the same or different carriers.

  • Exterior Drainage Does water stand on the property for more than 24 hours after a heavy rain? Yes No Unknown Comments Are gutters and downspouts in good repair? Yes No Unknown Comments:

  • Temporary Structures Installation of temporary construction-related structures including scaffolding, barriers, screening, fences, protective walkways, signage, office trailers or restrooms.

  • Walls 12 Developer shall provide rustication patterns on all walls, except drainage headwalls, in Aesthetic 13 Area 3 in accordance with Exhibit L2.24 of the LAADCR. The final designs shall resemble these 14 simulations.

  • Unbundled Loop Modifications (Line Conditioning 2.5.1 Line Conditioning is defined as routine network modification that BellSouth regularly undertakes to provide xDSL services to its own customers. This may include the removal of any device, from a copper Loop or copper Sub-loop that may diminish the capability of the Loop or Sub-loop to deliver high-speed switched wireline telecommunications capability, including xDSL service. Such devices include, but are not limited to, load coils, excessive bridged taps, low pass filters, and range extenders. Excessive bridged taps are bridged taps that serves no network design purpose and that are beyond the limits set according to industry standards and/or the XxxxXxxxx XX 00000.

Time is Money Join Law Insider Premium to draft better contracts faster.