Main Meter / Check Meter comparison. (A) Metering data recorded by the Main Meter and Check Meter must be compared on a half-hourly basis. Allowance shall be made for low load discrepancies. (B) Any discrepancy between the two values in excess of 1.5 times the accuracy requirements prescribed for the individual Meters at full load in accordance with the TSRs must be investigated further by the Generator.

Appears in 8 contracts

Samples: Private Network CFD Agreement, Private Network CFD Agreement, Private Network CFD Agreement

AutoNDA by SimpleDocs

Main Meter / Check Meter comparison. (A) 13.2.1 Metering data recorded by the Main Meter and Check Meter must be compared on a half-hourly basis. Allowance shall be made for low load discrepancies. (B) 13.2.2 Any discrepancy between the two values in excess of 1.5 times the accuracy requirements prescribed for the individual Meters at full load in accordance with the TSRs must be investigated further by the Generator.

Appears in 2 contracts

Samples: Private Network Metering Operational Framework, Private Network CFD Agreement