Metering Power and Communications Requirements. i. Revenue meters, ancillary equipment and communications equipment will be provided with 120 A.C. and 125v D.C. auxiliary power from the LIPA 8ER Brookhaven Substation control house. ii. LIPA shall provide and maintain two (2) dial up, dedicated, voice grade telephone lines with required station protection and isolation for the LIPA revenue metering. iii. The Large Generating Facility shall provide a dedicated lease line for communications between the RTU located in 9WU-BNL and LIPA’s Hicksville Operations Center; aside from this item, all other equipment in this Appendix (A)(1)(B) will be procured and installed by LIPA. iv. A fiber optic conduit stubout 5 feet beyond fence line will be provided by LIPA. The new fiber optic communication line will be terminated and tested at a newly installed patch panel inside the existing control house.