Monitoring Points Clause Samples
POPULAR SAMPLE Copied 1 times
Monitoring Points. In order to monitor settlement and vibration within the Site and the vicinity thereof, the Contractor shall install and maintain appropriate monitoring points including extensometers, vibration monitoring systems, vibration wire strain gauges, piezometers, ground settlement markers and building settlement markers, etc. Some of the monitoring points may be located outside the boundary of the Site. The Contractor is responsible for obtaining the necessary consents, permits and access from the relevant authorities and building owners, and to allow continued maintenance of such points throughout the entire Contract Period. All monitoring points shall be maintained at all times during the contract period.
Monitoring Points. ▇▇▇▇▇▇▇▇▇▇▇ ▇-▇, ▇-▇, ▇▇-▇, ▇▇-▇, ▇▇-▇▇, ▇-▇, ▇▇-▇▇, MW3-2R, ▇▇-▇, ▇▇-▇, ▇▇-▇, ▇▇-▇, ▇▇▇-▇, UPG-2 MW-4 and MW-4P are in close proximity, therefore only one well needs to be monitored for the parameters listed in Table A. The other well (MW-4P) is intended as a piezometer well and shall be monitored for water elevation only. MW-4 is considered a POC well. ▇▇▇▇▇ ▇▇▇-▇, ▇▇▇-▇, and MW-3 shall be monitored for water elevation only.
Monitoring Points. Leachate-Impacted Groundwater ▇-▇, ▇-▇▇, ▇-▇▇, ▇-▇, P-2A, P3-PZ, ▇-▇, ▇▇-▇-▇▇, ▇-▇, ▇▇-▇, ▇▇-▇▇*, ▇▇▇-▇▇, ▇▇-▇*, ▇▇-▇▇, PZ-3A*, PZ-3B*, PZ-3C All ▇▇▇▇▇ shall be monitoring for water elevation. All ▇▇▇▇▇ shall be monitored for chemical constituents outlined in Table A (Attached) once every 5 Years. ▇▇▇▇▇ denoted with an asterisk (*) shall be monitored for leachate elevations only.
Monitoring Points. 3.5.1. Each transmitter shall be equipped with output monitoring points as follows:- • At the intermediate frequency [if applicable], • On each of the final power amplifiers, • After the amplifier output combiner, • After the band pass output filter • A sample of the local oscillator frequency.
3.5.2. The output monitor points must be calibrated and shall be fed from directional couplers with a directivity of at least 30dB.
3.5.3. The source impedance of such monitoring points shall be 50 ohm unbalanced and the output levels as high as appropriately possible, but not exceeding ten (10) milliwatts (0.707 Volts).
Monitoring Points. 11.1.1. The equipment shall be provided with monitoring facilities which the manufacturer regards as necessary for the alignment, testing, maintenance and operation of the transmitter or sections thereof.
11.1.2. If any additional software is required to download data or to repair/maintain the equipment locally, it must be included with the Transmitter price at no extra cost to Sentech.
