Phase Conductors And Neutral (Messenger) Resistance Test. The resistance of the phase conductors and the messenger shall be measured, the resistance is determined with direct current, the measured resistance is corrected to 20 c using the formulas and coefficients given in clause 5 of the standard I.E.C 60228, the values obtained shall not exceed resistance given in table NO. 7