Power Supply. 4.1 Provider will make power available to and in connection with the Customer Area up to the amount of the then-applicable Specified Power Draw, subject to Sections 4.5 and 4.6. 4.2 Customer acknowledges that the Specified Power Draw will be allocated to the Customer Area for the power usage of the Customer Equipment, the evaporative cooling of the Customer Area, as well as any other components that may be installed in the Customer Area that require power, such as additional cooling, air filtration, and monitoring equipment (i.e., it is allocated to the collective requirements of all components in the Customer Area that draw power). 4.3 Customer acknowledges that Provider may, but is under no obligation to, provide power beyond the Specified Power Draw. Provider has the right to power down Customer Equipment in the event that (i) the power draw of the Customer Area (including the evaporative cooling therefor) is, in the aggregate, reasonably likely to exceed the Specified Power Draw, or (ii) individual Hardware Units are reasonably likely to draw beyond the power usage per unit set forth in Section 1. 4.4 If a Ramp-Up Period is provided in Section 1, then for the applicable periods set forth therein the Specified Power Draw shall be deemed to be replaced with the values of the Temporary Power Draw. 4.5 Customer acknowledges that the power to the Facility is ultimately provided by third parties, whose provision and transmission of power is governed by Applicable Law, including but not limited to rules and regulations promulgated by the Electric Reliability Council of Texas, Inc., and the Public Utility Commission of Texas (collectively, the “Power Regulations”). To the extent that the available power to the Facility is reduced pursuant to Power Regulations, and such reductions are not due to the wrongful actions of Provider, Provider may reduce the power available to Customer to an amount that is less than the Specified Power Draw; provided that in such case, Provider shall not treat Customer, in any respect, less favorably than any similarly situated Provider customer. Any such reductions, and any unavailability of the Hosting Services arising out of such reductions, shall not be deemed to be unavailability for purposes of calculating Uptime under the Uptime Service Level. 4.6 Customer hereby expressly consents to Provider’s participation in any Demand Reduction Benefit Programs, as determined by Provider in its sole discretion. Customer acknowledges that any such participation may result in partial or complete reduction in power available to Customer from time to time, and that Provider may reduce the power available to Customer to an amount that is less than the Specified Power Draw. Any such reductions, and any unavailability of the Hosting Services arising out of such reductions, shall not be deemed to be unavailability for purposes of calculating Uptime under the Uptime Service Level. 4.7 Customer acknowledges that Provider’s right to participate in any Demand Reduction Benefit Programs, as determined by Provider in its sole discretion, forms an essential basis of the agreements set forth in this Agreement, and that, absent such right, the terms of this Agreement, including the Hosting Charges, would be substantially different. 4.8 Customer hereby expressly consents to the use of the Power Firmware in connection with the foregoing Demand Reduction Benefit Programs.
Appears in 3 contracts
Samples: Hosting Agreement (SilverSun Technologies, Inc.), Hosting Agreement (Rhodium Enterprises, Inc.), Hosting Agreement (Rhodium Enterprises, Inc.)
Power Supply. 4.1 Provider will make power available to and in connection with the Customer Area up to the amount of the then-applicable Specified Power Draw, subject to Sections 4.5 and 4.6.
4.2 Customer acknowledges that the Specified Power Draw will be allocated to the Customer Area for the power usage of the Customer Equipment, the evaporative cooling of the Customer Area, as well as any other components that may be installed in the Customer Area that require power, such as additional cooling, air filtration, and monitoring equipment power (i.e., it is allocated to the collective requirements of all components in the Customer Area that draw power).
4.3 Customer acknowledges that Provider may, but is under no obligation to, provide power beyond the Specified Power Draw. Provider has the right to power down Customer Equipment in the event that (i) the power draw of the Customer Area (including the evaporative evaporating cooling therefor) is, in the aggregate, reasonably likely to exceed the Specified Power Draw, or (ii) individual Hardware Units are reasonably likely to draw beyond the power usage per unit set forth in Section 1.
4.4 If a Ramp-Up Period is provided in Section 1, then for the applicable periods set forth therein the Specified Power Draw shall be deemed to be replaced with the values of the Temporary Power Draw.
4.5 Customer acknowledges that the power to the Facility is ultimately provided by third parties, whose provision and transmission of power is governed by Applicable Law, including but not limited to rules and regulations promulgated by the Electric Reliability Council of Texas, Inc., and the Public Utility Commission of Texas (collectively, the “Power Regulations”). To the extent that the available power to the Facility is reduced pursuant to Power Regulations, and such reductions are not due to the wrongful actions of Provider, Provider may reduce the power available to Customer to an amount that is less than the Specified Power Draw; provided that in such case, Provider shall not treat Customer, in any respect, less favorably than any similarly situated Provider customer. Any such reductions, Such reductions shall be considered and included in all respects in connection with any unavailability calculation of the Hosting Services arising out of such reductions, shall not be deemed to be unavailability for purposes of calculating Uptime performance under the Uptime Service Level.
4.6 Customer hereby expressly consents to Provider’s participation in any Demand Reduction Benefit Programs, as determined by Provider in its sole discretion. Customer acknowledges that the requirements of any such participation may result in Demand Reduction Benefit Program could lead to a complete or partial or complete reduction in power available to Customer from time to timesuspension of the Services; provided, and however, that Provider may reduce the power available to Customer to an amount that is less than the Specified Power Draw. Any such reductions, and any unavailability of the Hosting Services (as contemplated under Section 8) arising out of any such reductions, shall participation is not be deemed to be unavailability excused for purposes of calculating Uptime under . Provider shall allocate the Uptime Service Level.
4.7 Customer acknowledges impact of any Demand Reduction Benefit Program across the customers of the Facility on a pro rata basis, based on their respective Specified Power Draw amounts. Any savings in power costs that Providermay be realized from the Facility’s right to participate participation in any Demand Reduction Benefit ProgramsPrograms will be considered a rebate subject to the provisions of Section 6.7 of this Agreement. 5 Access to the Facility; Data Center Rules
5.1 Customer Representatives may access the Customer Area of the Facility during Working Hours, as determined by in accordance with the Data Center Rules, for the purpose of conducting inspections relating to Customer Equipment. To obtain such access, Customer must deliver prior written notice to Provider in its accordance with the Data Center Rules, and in no event later than [***] Business Days prior to the date of such access. Notwithstanding anything to the contrary, Provider shall have the right to remove any Customer Representative from the Facility premises in Provider’s sole discretion, forms an essential basis of the agreements set forth in this Agreementat any time, and that, absent such right, the terms of this Agreement, including the Hosting Charges, would be substantially differentwithout any liability to Customer or any Customer Representative.
4.8 5.2 Customer, and the Customer hereby expressly consents to the use of the Power Firmware Representatives, shall comply with all Data Center Rules in connection with such access. Customer shall inform each applicable Customer Representative of the foregoing Demand Reduction Benefit ProgramsData Center Rules prior to such Customer Representative accessing the Facility. Customer shall be liable for the acts and omissions of all Customer Representatives who access, or attempt to access, the Facility, including for their violation of the Data Center Rules, at least to the same extent as if such acts and omissions were Customer’s own.
Appears in 3 contracts
Samples: Colocation Agreement (SilverSun Technologies, Inc.), Colocation Agreement (Rhodium Enterprises, Inc.), Colocation Agreement (Rhodium Enterprises, Inc.)
Power Supply. 4.1 Provider will make power available to and in connection with the Customer Area up to the amount of the then-applicable Specified Power Draw, subject to Sections 4.5 and 4.6.
4.2 Customer acknowledges that the Specified Power Draw will be allocated to the Customer Area for the power usage of the Customer Equipment, the evaporative cooling of the Customer Area, as well as any other components that may be installed in the Customer Area that require power, such as additional cooling, air filtration, and monitoring equipment (i.e., it is allocated to the collective requirements of all components in the Customer Area that draw power).
4.3 Customer acknowledges that Provider may, but is under no obligation to, provide power beyond the Specified Power Draw. Provider has the right to power down Customer Equipment in the event that (i) the power draw of the Customer Area (including the evaporative cooling therefor) is, in the aggregate, reasonably likely to exceed the Specified Power Draw, or (ii) individual Hardware Units are reasonably likely to draw beyond the power usage per unit set forth in Section 1.
4.4 If a Ramp-Up Period is provided in Section 1, then for the applicable periods set forth therein the Specified Power Draw shall be deemed to be replaced with the values of the Temporary Power Draw.
4.5 Customer acknowledges that the power to the Facility is ultimately provided by third parties, whose provision and transmission of power is governed by Applicable Law, including but not limited to rules and regulations promulgated by the Electric Reliability Council of Texas, Inc., and the Public Utility Commission of Texas (collectively, the “Power Regulations”). To the extent that the available power to the Facility is reduced pursuant to Power Regulations, and such reductions are not due to the wrongful actions of Provider, Provider may reduce the power available to Customer to an amount that is less than the Specified Power Draw; provided that in such case, Provider shall not treat Customer, in any respect, less favorably than any similarly situated Provider customer. Any such reductions, and any unavailability of the Hosting Services arising out of such reductions, shall not be deemed to be unavailability for purposes of calculating Uptime under the Uptime Service Level.
4.6 Customer hereby expressly consents to Provider’s participation in any Demand Reduction Benefit Programs, as determined by Provider in its sole discretion. Customer acknowledges that any such participation may result in partial or complete reduction in power available to Customer from time to time, and that Provider may reduce the power available to Customer to an amount that is less than the Specified Power Draw. Any such reductions, and any unavailability of the Hosting Services arising out of such reductions, shall not be deemed to be unavailability for purposes of calculating Uptime under the Uptime Service Level.
4.7 Customer acknowledges that Provider’s right to participate in any Demand Reduction Benefit Programs, as determined by Provider in its sole discretion, forms an essential basis of the agreements set forth in this Agreement, and that, absent such right, the terms of this Agreement, including the Hosting Charges, would be substantially different.
4.8 Customer hereby expressly consents to the use of the Power Firmware in connection with the foregoing Demand Reduction Benefit Programs. 5 Access to the Facility; Data Center Rules
5.1 Customer Representatives may access the Customer Area of the Facility during Working Hours, in accordance with the Data Center Rules, for equipment inspections, installation, removal, additions, subtractions or physical maintenance or otherwise by prior appointment as mutually agreed. To obtain such access, Customer must provide prior notice to Provider in accordance with the Data Center Rules, and coordinate with Provider so that all such access may be escorted. Notwithstanding anything to the contrary, Provider shall have the right to remove any Customer Representative from the Facility premises in Provider’s sole discretion, at any time, and without any liability to Customer or any Customer Representative.
5.2 Customer, and the Customer Representatives, shall comply with all Data Center Rules in connection with such access. Customer shall inform each applicable Customer Representative of the Data Center Rules prior to such Customer Representative accessing the Facility. Customer shall be liable for the acts and omissions of all Customer Representatives who access, or attempt to access, the Facility, including for their violation of the Data Center Rules, at least to the same extent as if such acts and omissions were Customer’s own.
Appears in 3 contracts
Samples: Hosting Agreement (SilverSun Technologies, Inc.), Hosting Agreement (Rhodium Enterprises, Inc.), Hosting Agreement (Rhodium Enterprises, Inc.)
Power Supply. 4.1 4.1. Provider will make power available to and in connection with the Customer Area up to the amount of the then-applicable Specified Power Draw, subject to Sections 4.5 the terms of this Section 4 and 4.6.
4.2 Customer acknowledges Uptime requirements as specified in Section 8.1 of this Agreement; provided, however, that notwithstanding anything to the Specified Power Draw will be allocated contrary, Provider shall have no obligation to make power available to the Customer Area Equipment in excess of approximately [***], or sufficient power to achieve the Manufacturer Specified Hashrate for the power usage of the Customer Equipment, the evaporative cooling of the Customer Area, as well as any other components that may be installed in the Customer Area that require power, such as additional cooling, air filtration, and monitoring equipment (i.e., it is allocated to the collective requirements of all components in the Customer Area that draw power)each Active Bitcoin Miner.
4.3 4.2. Customer acknowledges that Provider may, but is under no obligation to, provide power beyond the Specified Power Draw, notwithstanding the Uptime requirements as specified in Section 8.1 of this Agreement. Customer further acknowledges that Provider has the right right, in its commercially reasonable discretion, to power down Customer Equipment in the event that (i) the power draw of the Customer Area (including the evaporative immersion cooling therefor) is, in the aggregate, reasonably likely to exceed the Specified Power Draw, or (ii) individual Hardware Units are reasonably likely to draw beyond the power usage per unit set forth in Section 1Hardware Unit designated for such Hardware Units.
4.4 If a Ramp-Up Period is provided in Section 1, then for the applicable periods set forth therein the Specified Power Draw shall be deemed to be replaced with the values of the Temporary Power Draw.
4.5 4.3. Customer acknowledges that the power to the Facility is ultimately provided by Governmental Authorities and other third parties, whose provision and transmission of power is governed by Applicable Law, including but not limited to rules and regulations promulgated by the Electric Reliability Council of Texas, Inc., ERCOT and the Public Utility Commission of Texas (collectively, the “Power Regulations”). To the extent that the available power to the Facility is reduced pursuant to Power Regulations, a Force Majeure Event or an Outage, and such reductions are not due to the wrongful actions gross negligence or willful misconduct of Provider, Provider may reduce the power available to Customer to an amount that is less than the Specified Power Draw; provided that in such case, Provider shall not treat Customer, in any respect, less favorably than any similarly situated Provider customer. Any such reductions, and any unavailability of the Hosting Services arising out of such reductions, shall not be deemed to be unavailability for purposes of calculating Uptime under the Uptime Service Level; provided, that any Planned Outages in excess of [***] per year shall be deemed to be unavailability for purposes of calculating Uptime under the Uptime Service Level, except as approved by Customer where such approval shall not be unreasonably withheld. It is expressly agreed that Provider may voluntarily reduce availability at its sole discretion, and such reduction shall not be deemed availability for purposes of calculating Uptime under the Uptime Service Level. To the extent that any voluntary unavailability results in the Uptime Service Level to not be met, then the calculations set forth in Section 8.4 for applicable compensation to Customer shall apply.
4.6 4.4. Customer hereby expressly consents to Provider’s participation in the ERCOT Ancillary Services markets and/or any Demand Reduction Benefit Programs, as determined by Provider in its sole discretion. Customer acknowledges that any such participation may result in partial or complete reduction in power available to Customer from time to time, and that Provider may reduce the power available to Customer to an amount that is less than the Specified Power DrawDraw (and Provider shall have no liability to Customer in connection with any such reduction or unavailability, except as otherwise contemplated herein). Any such reductions, and any unavailability of the Hosting Services arising out of such reductions, shall not be deemed to be unavailability for purposes of calculating Uptime under the Uptime Service Level.
4.7 ; provided, that any reductions for Ancillary Services in excess of [***] per year shall be deemed to be unavailability for purposes of calculating Uptime under the Uptime Service Level, except as approved by Customer where such approval shall not be unreasonably withheld. Customer acknowledges that Provider’s right to participate in any Demand Reduction Benefit Programs, as determined by Provider in its sole discretion, forms an essential basis of the agreements set forth in this Agreement, and that, absent such right, the terms of this Agreement, including the Hosting ChargesMiner Charge, would be substantially different.
4.8 . Furthermore, Customer hereby expressly consents to the use of the Power Firmware in connection with the foregoing ERCOT Ancillary Services markets and/or Demand Reduction Benefit Programs.