REQUIRED STANDARDS. The Member must certify the following requirements: 5.2.1 The installation of the Generator and all equipment in the system must comply with the latest published edition of IEEE 929 and IEEE 1547 as applicable. 5.2.2 Future IEEE Standards and/or Recommended Practices: IEEE P1547.1, P1547.2 and P1547.3 are still proposed draft documents and still in working groups at the time of writing this Standard. Generators interconnected after these standards are published may be required to comply with these IEEE documents. 5.2.3 The Member’s inverter or interconnection protection system must be tested and listed for compliance with the latest published edition of Underwriters Laboratories, Inc. (UL) 1741. 5.2.4 The Generator must pass the anti-islanding test in UL 1741. 5.2.5 The Member’s inverter or interconnection protection system must be manufactured after November 7, 2000. 5.2.6 Any protection settings affecting anti-islanding performance must not be adjusted after passing anti-islanding tests; and the anti-islanding device cannot be disabled or bypassed.