Common use of Under-Frequency and Over Frequency Conditions Clause in Contracts

Under-Frequency and Over Frequency Conditions. The New York State Transmission System is designed to automatically activate a load-shed program as required by the NPCC in the event of an under-frequency system disturbance. Developer shall implement under-frequency and over-frequency relay set points for the Large Generating Facility as required by the NPCC to ensure “ride

Appears in 3 contracts

Samples: Standard Large Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement

AutoNDA by SimpleDocs

Under-Frequency and Over Frequency Conditions. The New York State Transmission System is designed to automatically activate a load-shed program as required by the NPCC in the event of an under-frequency system disturbance. Developer shall implement under-frequency and over-frequency relay set points for the Large Generating Merchant Transmission Facility as required by the NPCC to ensure “ride

Appears in 2 contracts

Samples: Interconnection Agreement, Interconnection Agreement

Under-Frequency and Over Frequency Conditions. The New York State Transmission System is designed to automatically activate a load-shed program as required by the NPCC in the event of an under-frequency system disturbance. Developer shall implement under-frequency and over-frequency relay set points for the Large Generating Facility Transmission Project as required by the NPCC to ensure the “ride

Appears in 2 contracts

Samples: Transmission Facility Interconnection Agreement, Transmission Facility Interconnection Agreement

Under-Frequency and Over Frequency Conditions. The New York State Transmission System is designed to automatically activate a load-load- shed program as required by the NPCC in the event of an under-frequency system disturbance. Developer shall implement under-frequency and over-over- frequency relay set points for the Large Generating Facility as required by the NPCC to ensure “rideride through” capability of the New York State Transmission System. Large Generating Facility response to frequency deviations of predetermined magnitudes, both under-frequency and over-

Appears in 1 contract

Samples: Interconnection Agreement

Under-Frequency and Over Frequency Conditions. The New York State Transmission System is designed to automatically activate a load-shed program as required by the NPCC in the event of an under-frequency system disturbance. Developer shall implement under-frequency and over-frequency relay set points for the Large Generating Facility as required by the NPCC to ensure “rideLarge

Appears in 1 contract

Samples: Interconnection Agreement

AutoNDA by SimpleDocs

Under-Frequency and Over Frequency Conditions. The New York State Transmission System is designed to automatically activate a load-shed program as required by the NPCC in the event of an under-frequency system disturbance. Developer shall implement under-frequency and over-frequency relay set points for the Large Generating GeneratingMerchant Transmission Facility as required by the NPCC to ensure “rideride through” capability of the New York State Transmission System. Large GeneratingMerchant Transmission Facility response to frequency

Appears in 1 contract

Samples: Interconnection Agreement

Under-Frequency and Over Frequency Conditions. The New York State Transmission System is designed to automatically activate a load-shed loadshed program as required by the NPCC in the event of an under-frequency system disturbance. Developer shall implement under-frequency and over-frequency relay set points for the Large Generating Facility as required by the NPCC to ensure “rideLarge

Appears in 1 contract

Samples: Large Generator Interconnection Agreement