Common use of Wind Speed and Wind Direction Clause in Contracts

Wind Speed and Wind Direction. The wind direction and wind speed are integral components of the calculation of flexible substation bus thermal ratings. Wind direction perpendicular to the conductor (a 90-degree cross wind) shall be used and a wind speed up to 3 fps shall be allowed.

Appears in 2 contracts

Samples: www.iso-ne.com, www.iso-ne.com

AutoNDA by SimpleDocs

Wind Speed and Wind Direction. The wind direction and wind speed are integral components of the calculation of flexible substation bus Rigid Substation Bus thermal ratings. Wind direction perpendicular to the conductor (a 90-degree cross wind) shall be utilized. With regard to wind speed, IEEE Standard 605-2008 includes the mathematical models to be used and to calculate Substation Rigid Bus thermal ratings, where a wind speed of 2 fps is used. However, for New England, a wind speed up to 3 fps shall be allowed.

Appears in 2 contracts

Samples: www.iso-ne.com, www.iso-ne.com

AutoNDA by SimpleDocs
Time is Money Join Law Insider Premium to draft better contracts faster.