Common use of Ephratah Substation Clause in Contracts

Ephratah Substation. All modifications shall be completed in the Ephratah Substation yard. However, since the existing relay panels are full and there is no space to install new equipment, an outdoor relay enclosure on a reinforced concrete foundation will be required to house the equipment required for interconnection of the Small Generating Facility. The Ephratah Substation’s control house, and the associated battery system, are owned and operated by Brookfield Hydro (“Brookfield”) but are shared-use facilities. As such, Connecting Transmission Owner will coordinate with Brookfield on any changes made inside the control house. The System Upgrade Facilities described in this section assume that DC circuit for the relay cabinet will be provided from the existing shared-use battery system and that Connecting Transmission Owner will coordinate provisioning of the circuit with Brookfield. If it is determined during final engineering that the DC circuit cannot be provided by the existing battery system, then the Connecting Transmission Owner shall install a separate battery system in an enclosure in the vicinity of the new relay cabinet. All costs associated with this would be the responsibility of the Interconnection Customer. A new AC circuit will be required to power the heat in the relay cabinet.

Appears in 5 contracts

Samples: Interconnection Agreement, Service Agreement, Interconnection Agreement