Common use of Flow and Tamper Devices Clause in Contracts

Flow and Tamper Devices. a. Visually inspect for damage b. Test by opening the inspection test valve on the sprinkler system (Retard should be 90 seconds or less) c. Verify proper zone annunciation d. Test for proper operation in trouble condition by removing wire from the device (at the device, not the panel) (1) Test that removal of tamper switch cover initiates a trouble report (2) Adjust devices in accordance with the manufacturer's specifications

Appears in 4 contracts

Samples: Facility Security Equipment, Systems and Services, Subordinate Contract for Facility Security Equipment, Systems and Services, Fire Alarm System Maintenance Repair Contract

AutoNDA by SimpleDocs

Flow and Tamper Devices. a. Visually inspect for damage b. Test by opening the inspection test valve on the sprinkler system (Retard should be 90 seconds or less) c. Verify proper zone annunciation d. Test for proper operation in trouble condition by removing wire from the device (at the device, not the panel) (1) Test that removal of tamper switch cover initiates a trouble report (2) Adjust devices in accordance with the manufacturer's specifications e. Visual Inspection and testing of: (1) Water Flow Devices (2) Tamper Devices (3) Control Valve Devices (4) Pressure Devices

Appears in 2 contracts

Samples: Subordinate Contract for Facility Security Equipment, Systems and Services, Fire Alarm System Maintenance Repair Contract

Flow and Tamper Devices. a. Visually inspect for damage b. Test by opening the inspection test valve on the sprinkler system (Retard should be 90 seconds or less) c. Verify proper zone annunciation d. Test for proper operation in trouble condition by removing wire from the device (at the device, not the panel) (1) Test that removal of tamper xxxxxx switch cover initiates a trouble report (2) Adjust devices in accordance with the manufacturer's specifications e. Visual Inspection and testing of: (1) Water Flow Devices (2) Tamper Devices (3) Control Valve Devices (4) Pressure Devices

Appears in 1 contract

Samples: Subordinate Contract for Facility Security Equipment, Systems and Services

AutoNDA by SimpleDocs

Flow and Tamper Devices. a. Visually inspect for damage b. Test by opening the inspection test valve on the sprinkler system (Retard should be 90 seconds or less) c. Verify proper zone annunciation d. Test for proper operation in trouble condition by removing wire from the device (at the device, not the panel) (1) Test that removal of tamper xxxxxx switch cover initiates a trouble report (2) Adjust devices in accordance with the manufacturer's specifications

Appears in 1 contract

Samples: Subordinate Contract for Facility Security Equipment, Systems and Services

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!