Governor Characteristics. The Facility shall be capable of providing an immediate and sustained response to abnormal frequency excursions within the machine design parameters. The governors shall be properly maintained and shall provide droop characteristics consistent with the requirements of NERC, SERC and the Georgia Power Electric System. At a minimum, governors shall be fully responsive to frequency deviations consistent with the requirements of NERC, SERC and the Georgia Power Electric System during normal operating conditions only, as defined by Good Utility Practices. In no event shall the governors be blocked by Generator without the express written permission of Georgia Power.
Appears in 4 contracts
Samples: Interconnection Agreement (Southern Power Co), Interconnection Agreement (Southern Power Co), Interconnection Agreement (Southern Power Co)
Governor Characteristics. The Facility shall be capable of providing an immediate and sustained response to abnormal frequency excursions within the machine design parameters. The governors shall be properly maintained and shall provide droop characteristics consistent with the requirements of NERC, SERC and the Georgia Power Electric SystemSouthern Company control area. At a minimum, governors shall be fully responsive to frequency deviations consistent with the requirements of specified by NERC, SERC and the Georgia Power Electric System Southern Company control area during normal operating conditions only, as defined by Good Utility Practices. In no event shall the governors be blocked by Generator Tenaska without the express written permission of Georgia Power.. Appendix A
Appears in 1 contract
Samples: Interconnection Agreement (Tenaska Georgia Partners Lp)