Harmonics. The Facility shall not introduce excessive distortion to the Georgia Power Electric System's voltage profile and current waveforms. The harmonic distortion measurements shall be made at the transmission facility serving the Facility and be within the limits specified in the tables below.
Appears in 4 contracts
Samples: Interconnection Agreement (Southern Power Co), Interconnection Agreement (Southern Power Co), Interconnection Agreement (Southern Power Co)
Harmonics. The Facility shall not introduce excessive distortion to the Georgia Power Electric System's voltage profile and current waveforms. The harmonic distortion measurements shall be made at the transmission facility serving the Facility and be within the limits specified in the tables below.
Appears in 1 contract