Common use of Inghams Station Clause in Contracts

Inghams Station. The Transmission Owner will design and construct System Upgrade Facilities at Inghams Station, including line Relay Protection Packages associated with the addition of the Interconnection Station in the existing 115 kV Valley - Inghams #3 line. The following required detail modifications are associated with the #3 Valley-Inghams Line and the changes as a result of the #3 Line being split to accommodate the Fairfield Station. All modifications will adhere to NPCC Document A-5: Bulk Power System Protection Criteria. A new POTT relaying system is recommended using the existing OPTIMHO relay to provide required primary pilot protection for the new line section. The communication medium will be either a leased telephone line, if available, or, if the leased telephone line is not available, another new power line carrier channel.