Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one (1) 18kV circuit breaker. • Install two (2) 18kV/345kV generator step-up transformers. • Install two (2) 345kV circuit breakers and disconnect switches. • Install Relaying and Metering per ComEd standards. (2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one One (1) 18kV 115/34.5/13.8 kV wye grounded / wye grounded / delta main power transformer with a rating of 57/76/95 MVA; • One (1) 115 kV circuit breaker. ; • Install two One (21) 18kV/345kV generator step-up transformers. 18 MVAR capacitor bank; and • Install two (2) 345kV circuit breakers and disconnect switches. • Install Relaying and Metering per ComEd standardsCommunication equipment to the Interconnected Transmission Owner bidirectional metering equipment.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one :
1. One (1) 18kV fully rated 34.5 kV circuit breaker. • Install two (2) 18kV/345kV generator breaker on the high side of AC1-039 step-up transformerstransformer.
2. • Install two The required Interconnected Transmission Owner generation interconnection relaying and control facilities.
3. The supervisory control and data acquisition (2SCADA) 345kV circuit breakers and disconnect switchesequipment.
4. • Install Relaying and Metering per ComEd standardsThe establishment of dedicated communication circuits for SCADA.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None None. Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one One (1) 18kV circuit breaker. • Install two (2) 18kV/345kV generator 34.5/345 kV grounded wye / grounded wye main step-up transformers. transformer; • Install two Relay and protective equipment, supervisory control and data acquisition (2SCADA) 345kV circuit breakers equipment, fiber-optic equipment, and disconnect switches. telecommunications equipment; and • Install Relaying and Metering per ComEd standardsNecessary metering equipment as specified in Schedule C of this ISA.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one One (1) 18kV 230/34.5 kV wye ground/delta main power transformer with a rating of 54/72/90 MVA; • 2 x 00 XXxx xxx 0x 0 XXxx xxxxxxxxx xxxxx; • One (1) 230 kV circuit breaker. ; and • Install two (2) 18kV/345kV generator step-up transformers. • Install two (2) 345kV circuit breakers and disconnect switches. • Install Relaying and Metering per ComEd standardsCommunication equipment to the Interconnected Transmission Owner bidirectional metering equipment.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one (1) 18kV One 115 kV wye grounded / 34.5 kV wye grounded main power transformer; • Three 34.5 kV circuit breakers; • 18MVar, 34.5kV Capacitor bank; • One 115 kV circuit breaker. ; and • Install two (2) 18kV/345kV generator step-up transformers. • Install two (2) 345kV circuit breakers and disconnect switches. • Install Relaying and Metering per ComEd standardsCommunication equipment to the Interconnected Transmission Owner bidirectional metering equipment.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one One (1) 18kV circuit breaker. • Install two (2) 18kV/345kV generator 138/34.5 kV grounded wye / grounded wye main step-up transformerstransformer; • One (1) 138 kV circuit breaker; and • 138 kV generator lead transmission line from the step-up transformer to the Point of Interconnection. • Install two (2) 345kV circuit breakers and disconnect switches. • Install Relaying and Metering per ComEd standardsNecessary metering equipment as specified in Schedule C of this ISA.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one One (1) 18kV 115/34.5 kV wye ground/delta main power transformer with a rating of 48/64/80 MVA; • 2 x 12 MVar and 1x 6 MVar capacitor banks; • One (1) 115 kV circuit breaker. ; and • Install two (2) 18kV/345kV generator step-up transformers. • Install two (2) 345kV circuit breakers and disconnect switches. • Install Relaying and Metering per ComEd standardsCommunication equipment to the Interconnected Transmission Owner bidirectional metering equipment.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one One (1) 18kV 230/34.5 kV wye ground/delta main power transformer with a rating of 54/72/90 MVA; • 2 x 12 MVar and 1x 6 MVar capacitor banks; • One (1) 230 kV circuit breaker. ; and • Install two (2) 18kV/345kV generator step-up transformers. • Install two (2) 345kV circuit breakers and disconnect switches. • Install Relaying and Metering per ComEd standardsCommunication equipment to the Interconnected Transmission Owner bidirectional metering equipment.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement
Interconnection Customer. (1) Interconnection Customer shall construct and, unless otherwise indicated, shall own, the following Interconnection Facilities: TSS 942 Xxxxxx Substation (Customer Interconnection Facility) • Install one (1) 18kV One 115 kV wye grounded / 34.5 kV wye grounded main power transformer; Three 34.5 kV circuit breakers; 18MVar, 34.5kV Capacitor bank; One 115 kV circuit breaker. • Install two (2) 18kV/345kV generator step-up transformers. • Install two (2) 345kV circuit breakers ; and disconnect switches. • Install Relaying and Metering per ComEd standards Communication equipment to the Interconnected Transmission Owner bidirectional metering equipment.
(2) In the event that, in accordance with the Interconnection Construction Service Agreement, Interconnection Customer has exercised the Option to Build, it is hereby permitted to build in accordance with and subject to the conditions and limitations set forth in that Section, the following portions of the Transmission Owner Interconnection Facilities which constitute or are part of the Customer Facility: None Ownership of the facilities built by Interconnection Customer pursuant to the Option to Build shall be as provided in the Interconnection Construction Service Agreement.
Appears in 1 contract
Samples: Interconnection Service Agreement