Power System Stabilizers. Interconnection Customer shall procure, install, maintain and operate power system stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve the right to reasonably establish minimum acceptable settings for any installed power system stabilizers, subject to the design and operating limitations of the Generating Facility. If the Generating Facility’s power system stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission Provider’s system operator, or its designated representative. The requirements of this paragraph shall not apply to induction generators.
Appears in 29 contracts
Samples: Generator Interconnection Agreement (Gia), Generator Interconnection Agreement (Gia), Generator Interconnection Agreement
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Large Generating Facility. If the Large Generating Facility’s power system stabilizers 's Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission Provider’s 's system operator, or its designated representative. The requirements of this paragraph shall not apply to induction wind generators.
Appears in 23 contracts
Samples: Surplus Large Generator Interconnection Agreement, Surplus Large Generator Interconnection Agreement, Standard Large Generator Interconnection Agreement (Lgia)
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Generating Facility. If the Generating Facility’s power system stabilizers 's Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission ProviderOwner’s system operator, or its designated representative. The requirements of this paragraph shall not apply to induction wind generators.
Appears in 10 contracts
Samples: Settlement Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Large Generating Facility. If the Large Generating Facility’s power system stabilizers Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission Provider’s system operator, or its designated representative. The requirements of this paragraph shall not apply to induction wind generators.
Appears in 9 contracts
Samples: Small Generator Interconnection Agreement (Sgia), Standard Large Generator Interconnection Agreement (Lgia), Standard Large Generator Interconnection Agreement
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve the right to reasonably establish minimum acceptable settings for any installed power system stabilizers, subject to the design and operating limitations of the Generating Facility. If the Generating Facility’s power system stabilizers are removed from service or are not capable of automatic operation, the Interconnection Customer shall immediately notify the Transmission Provider’s system operator, or its designated representative. The requirements of this paragraph shall not apply to induction generators.
Appears in 8 contracts
Samples: Large Generator Interconnection Agreement (ITC Holdings Corp.), Generator Interconnection Agreement, Generator Interconnection Agreement
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Large Generating Facility. If the Large Generating Facility’s power system stabilizers 's Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission Provider’s 's system operator, or its designated representative. The requirements of this paragraph shall not apply to induction generators.wind generators.
Appears in 6 contracts
Samples: Standard Large Generator Interconnection Agreement (Lgia), Standard Large Generator Interconnection Agreement (Lgia), Standard Large Generator Interconnection Agreement (Lgia)
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability CouncilStandards. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Generating Facility. If the Generating Facility’s power system stabilizers 's Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission Provider’s 's system operator, or its designated representative. The requirements of this paragraph shall not apply to induction wind generators.
Appears in 5 contracts
Samples: Standard Generator Interconnection Agreement (Sgia), Standard Generator Interconnection Agreement (Sgia), Standard Generator Interconnection Agreement (Sgia)
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Large Generating Facility. If the Large Generating Facility’s power system stabilizers 's Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission ProviderOwner’s system operator, or its designated representative. The requirements of this paragraph shall not apply to induction wind generators.
Appears in 4 contracts
Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Generating Facility. If the Generating Facility’s power system stabilizers 's Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission ProviderOwner’s system operator, or its designated representative. The requirements of this paragraph shall not apply to induction non-synchronous generators.
Appears in 3 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Interim Generator Interconnection Agreement
Power System Stabilizers. Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Electric Reliability CouncilCouncilOrganization. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Large Generating Facility. If the Large Generating Facility’s power system stabilizers 's Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission Provider’s 's system operator, or its designated representative. The requirements of this paragraph shall not apply to induction wind generators.
Appears in 2 contracts
Samples: Standard Large Generator Interconnection Agreement (Lgia), Standard Large Generator Interconnection Agreement (Lgia)
Power System Stabilizers. Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Large Generating Facility. If the Large Generating Facility’s power system stabilizers 's Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission Provider’s 's system operator, operator or its designated representative. The requirements of this paragraph shall not apply to induction wind generators.
Appears in 1 contract
Power System Stabilizers. The Interconnection Customer shall procure, install, maintain and operate power system stabilizers Power System Stabilizers, which includes synchronous machines, in accordance with the guidelines and procedures established by the Applicable Reliability Council. Transmission Provider and Transmission Owner reserve Operating Agent reserves the right to reasonably establish minimum acceptable settings for any installed power system stabilizersPower System Stabilizers, subject to the design and operating limitations of the Generating Facility. If the Generating Facility’s power system stabilizers Power System Stabilizers are removed from service or are not capable of automatic operation, Interconnection Customer shall immediately notify the Transmission ProviderOperating Agent’s system operator, or its designated representative. The requirements of this paragraph shall not apply to induction inverter based generators.
Appears in 1 contract