Revenue Metering. Connecting Transmission Owner-owned revenue metering will be located on the generator side of the 34.5kV breaker at the Bakerstand Solar Collector Substation and will consist of: • two (2) current transformers, GE type JKW-7; SERVICE AGREEMENT NO. 2572 • two (2) potential transformers, GE type JVW-7; and • one (1) revenue meter. (Note: Connecting Transmission Owner’s revenue metering current transformers/voltage transformers (“CT/VTs”) cannot be used to feed the Interconnection Customer’s check meter).
Appears in 4 contracts
Samples: Service Agreement, Service Agreement, Service Agreement
Revenue Metering. Connecting Transmission Owner-owned revenue metering will be located on the generator side of the 34.5kV breaker at the Bakerstand Solar Collector Substation and will consist of: • two (2) current transformers, GE type JKW-7; SERVICE AGREEMENT NO. 2572 • two (2) potential transformers, GE type JVW-7; and • one (1) revenue meter. (Note: Connecting Transmission Owner’s revenue metering current transformers/voltage transformers (“CT/VTs”) cannot be used to feed the Interconnection Customer’s check meter).;
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
Revenue Metering. Connecting Transmission Owner-owned revenue metering will be located on the generator side of the 34.5kV breaker at the Bakerstand Solar Collector Substation and will consist of: • two (2) current transformers, GE type JKW-7; SERVICE AGREEMENT NO. 2572 • two (2) potential transformers, GE type JVW-7; and • one (1) revenue meter. (Note: Connecting Transmission Owner’s revenue metering current transformers/voltage transformers (“CT/VTs”) cannot be used to feed the Interconnection Customer’s check meter).
Appears in 1 contract
Samples: Service Agreement