Sample Tests. Sample tests shall be required for cable manufacturer’s lengths in accordance with IEC 60502. One cable sample 10 meters long shall be cut from the completed cable and subjected to the following tests in the following sequence. a. Conductor examination, clause (17.4) b. Check of dimensions, clause (17.5, 6, 7, & 8) c. Voltage test for cables of rated voltage above 7.2 KV, clause (17.9). d. Hot set test for EPR, HEPR and, XPLE insulation and elastomeric sheaths, clause (17.10). e. galvanized wires tensile strength and thickness of galvanized coating according to approved latest B.S standard.
Appears in 7 contracts
Samples: Call Off Contract, Call Off Contract, Call Off Contract
Sample Tests. Sample tests shall be required for cable manufacturer’s lengths in accordance with IEC 60502. One cable sample 10 meters long shall be cut from the completed cable and subjected to the following tests in the following sequence.
a. Conductor examination, clause (17.4)
b. Check of dimensions, clause (17.5, 6, 7, & 8)
c. Voltage test for cables of rated voltage above 7.2 KV, clause (17.9).
d. Hot set test for EPR, HEPR and, XPLE insulation and elastomeric sheaths, clause (17.10).
e. galvanized Galvanized wires tensile strength and thickness of galvanized coating according to approved latest B.S standard.