Sewer System. 1. Minimum size for all sewer pipe shall be 8-inches except where line is less than 150 feet and will not be extended. 2. Minimum slope on all sewer pipe shall comply with Department of Ecology standards except for 8-inch. Minimum slope for 8-inch sewer pipe shall be 0.005 feet/foot except where a lesser slope is specifically approved by the City Engineer. 3. All sewer pipe invert elevations at manholes shall be computed to the center of the manhole. 4. Where the combined slope of the sewer line entering or exiting a manhole is less than

Appears in 6 contracts

Samples: Developer Extension Agreement, Developer Extension Agreement, Developer Extension Agreement

AutoNDA by SimpleDocs

Sewer System. 1. Minimum size for all sewer pipe shall be 8-inches except where line is less than 150 feet and will not be extended. 2. Minimum slope on all sewer pipe shall comply with Department of Ecology standards except for 8-inch. Minimum slope for 8-inch sewer pipe shall be 0.005 feet/foot except where a lesser slope is specifically approved by the City Engineer. 3. All sewer pipe invert elevations at manholes shall be computed to the center of the manhole. 4. Where the combined slope of the sewer line entering or exiting a manhole is less than