Xxxxxx Road Collector Substation Sample Clauses

Xxxxxx Road Collector Substation one (1) three phase, three winding, 115-34.5/13.8kV grounded wye/grounded wye/delta, tertiary step-up transformer rated 15/20/25MVA (ONAN/ONAF/ONAF), with impedance of 9.0%; • six (6) 96kV, 76kV maximum continuous operating voltage (“MCOV”) station class surge arresters; • one (1) 115kV, 1200A, 550kV basic insulation level (“BIL”) group operated air break switch; • one (1) 115kV, 1200A, 550kV BIL, 40kAIC SF-6 circuit breaker; • three (3) 115kV, 550kV BIL, voltage transformers (“VTs”), 0.3 W,X,Y,Z, 600/1000:1:1; • one (1) 38kV, 1200A, 150kV BIL group operated air break switch;
AutoNDA by SimpleDocs

Related to Xxxxxx Road Collector Substation

  • NETWORK INTERCONNECTION METHODS 3.1 The Interconnection provided herein may not be used solely for the purpose of originating a Party’s own interexchange traffic.

  • Interconnection 2.1 This section applies to linking with suppliers providing public telecommunications transport networks or services in order to allow the users of one supplier to communicate with users of another supplier and to access services provided by another supplier, where specific commitments are undertaken.