Examples of Rated Measuring Current in a sentence
Rated Measuring Current means the rated primary current of the current transformers in primary plant used for the purposes of measurement.
CONDITIONLIMIT OF ERRORS AT STATED SYSTEM POWER FACTORCurrent expressed as a percentage of Rated Measuring Current * Power Factor Limits of Error 100% to 20% inclusive Zero ± 4.0% 100% to 20% inclusive 0.866 lag and 0.866 ± 5.0% lead * for whole current metering percentage relates to Imax.
CONDITIONLIMIT OF ERRORS AT STATED SYSTEM POWER FACTORCurrent expressed as a percentage of Rated Measuring Current * Power Factor Limits of Error 100% to 20% inclusive Below 20% to 5% 100% to 20% inclusive 1 1 0.5 lag and 0.8 lead ± 1.5% ± 2.5% ± 2.5% Superseded * for whole current metering percentage relates to Imax.
These Meters shall meet the requirements of either BS EN 62053-22 Class 0.5S, or BS EN 62053-11 class 0.5 except where the overall accuracy as defined in Clause 4.2.1 is required in the range "Below 5% to 1%" of Rated Measuring Current.
CONDITIONLIMIT OF ERRORS AT STATED SYSTEM POWER FACTORCurrent expressed as a percentage of Rated Measuring Current Power Factor Limits of Error 120% to 10% inclusive Zero ± 4.0% 120% to 20% inclusive 0.866 lag and 0.866 ± 5.0% lead These limits of error for both (i) and (ii) above shall apply at the Reference Conditions defined in the appropriate Meter specification.
CONDITIONLIMIT OF ERRORS AT STATED SYSTEM POWER FACTORCurrent expressed as a percentage of Rated Measuring Current * Power Factor Limits of Error 100% to 20% inclusive 100% to 20% inclusive Zero 0.866 lag and 0.866 lead ± 4.0% ± 5.0% Superseded * for whole current metering percentage relates to Imax.
CONDITIONLIMIT OF ERRORS AT STATED SYSTEM POWER FACTORCurrent expressed as a percentage of Rated Measuring Current * Power Factor Limits of Error 100% to 20% inclusive 1 ± 1.5% Below 20% to 5% 1 ± 2.5% 100% to 20% inclusive 0.5 lag and 0.8 lead ± 2.5% * for whole current metering percentage relates to Imax.
CONDITIONLIMIT OF ERRORS AT STATED SYSTEM POWER FACTORCurrent expressed as a percentage of Rated Measuring Current * Power Factor Limits of Error 100% to 20% inclusive 100% to 20% inclusive Zero 0.866 lag and 0.866 lead ± 4.0% ± 5.0% * for whole current metering percentage relates to Imax.
CONDITIONLIMIT OF ERRORS AT STATED SYSTEM POWER FACTORCurrent expressed as a percentage of Rated Measuring Current Power Factor Limits of Error 120% to 10% inclusive 120% to 20% inclusive Zero 0.866 lag and 0.866 lead ± 4.0% ± 5.0% Superseded These limits of error for both (i) and (ii) above shall apply at the Reference Conditions defined in the appropriate Meter specification.
CONDITIONLIMIT OF ERRORS AT STATED SYSTEM POWER FACTORCurrent expressed as a percentage of Rated Measuring Current * Power Factor Limits of Error 100% to 20% inclusive 1 ± 1.5% Below 20% to 5% 1 ± 2.5% 100% to 20% inclusive 0.5 lag and 0.8 lead ± 2.5% SUPERSEDED * for whole current metering percentage relates to Imax.