Examples of Voltage Dip in a sentence
Additional features shall include Voltage Dip time delayNormal to Emergency and emergency to normal time delays.Load Dump Control on equipment branchesPhase Failure (In Phase) MonitorPanel mounted pilot lights and auxiliary contacts for remote pilot light status panel.Note: The complete PV installation of possible battery installation will be dealt with through a separate tender process.
Acetate-metal chelate rings have been demonstrated through a variety of experimental detection methods, including x-ray crystallography, extended x-ray absorption fine structure spectroscopy, infrared spectroscopy,and Raman spectroscopy.
Dynamic Voltage Dip Criteria Voltages at all busses on the Transmission Systems should not drop below 0.70 per unit after the first swing for more than 5 cycles.
An Event Estimate of Expenses will be prepared and will indicate the services desired, the price, and the authorization of the Licensee or designated representative.
The power generating system shall satisfy the following performance criteria at site conditions: Total Power Capability xxx Kw Frequency 60 Hz Voltage 480/2771/3 phase 4 wire Voltage Dip starting Largest Motor sequence 20% Power Factor 0.8 Overload for 1 Hour 10% C.
Current/Voltage harmonics generated by PIU industries affect the Distribution System on account of various parameters like Voltage Dip, Voltage flickers and Voltage & current waveform distortion, harmonics, capacity loss of the utility Distribution System, Demand Factor, Energy loss in Distribution System, etc.In view of above, as per existing instructions, following units/processes are considered Power Intensive Units (PIU).
And, following fault clearing, for transient and post-transient voltages remain within the following ranges: DisturbanceTransient Voltage Dip StandardPost Transient Voltage Deviation StandardN-1 (Single Contingency)Not to exceed 25% at load buses.Not to exceed 20% for more than 20 cycles at load buses.Not to exceed 5% at any bus.N-2 (DoubleContingency)Not to exceed 30% at any bus.Not to exceed 20% for more than 40 cycles at load buses.Not to exceed 10% atany bus.
And, following fault clearing, for transient and post-transient voltages remain within the following ranges: DisturbanceTransient Voltage Dip StandardPost Transient Voltage Deviation StandardN-1 (Single Contingency)Not to exceed 25% at load buses.Not to exceed 20% for more than 20 cycles at load buses.Not to exceed 5% at any bus.N-2 (Double Contingency)Not to exceed 30% at any bus.Not to exceed 20% for more than 40 cycles at load buses.Not to exceed 10% at any bus.
This may require the installation of surge arresters or spark gaps.2.3.3.4 Transient Voltage Dip Criteria (TVD)The transient voltage dip limits (following fault clearance), which may be used in assessing the network performance as a reference, are as follows.
NERC and WECCCategoriesOutage Frequency Associated with the Performance Category (outage/year) Transient Voltage Dip Standard Minimum Transient Frequency Standard Post Transient Voltage Deviation StandardASystem normalNot ApplicableNothing in addition to NERC BOne element out-of-service ≥ 0.33Not to exceed 25% at load buses or 30% at non-load buses.Not to exceed 20% for more than 20 cycles at load buses.