Compute RTO Generation Serving RTO Load Sample Clauses

Compute RTO Generation Serving RTO Load. Using the real-time generation output in MWs, compute the Generation serving RTO Load. Sum the output of RTO generation within each load zone: , for each RTO load zone Where: zone = the relevant RTO load zone; unit = the relevant generator; RTO_Genzone = the sum of the RTO’s generation in a zone; and Genunit,zone = the real-time output of the unit in a given zone. Next, reduce the RTO generation located within a load zone by the scheduled line real-time export transaction schedules that source from that particular load zone: Where: zone = the relevant RTO load zone; scheduled_line = each of the Transmission Facilities identified in Table 1 above; RTO_Reduced_Genzone = the sum of the RTO’s generation in a zone reduced by the sum of export schedules over scheduled lines from the zone; RTO_Genzone = the sum of the RTO’s generation in a zone; and Export_Schedulesscheduled_line,zone = export schedules from a zone over a scheduled line. The real-time export schedules over scheduled lines will only reduce the generation in the source zones identified in Table 1 above. The resulting generator output based on this reduction is defined below.
AutoNDA by SimpleDocs
Compute RTO Generation Serving RTO Load. Using the real-time generation output in MWs, compute the Generation serving RTO Load. Sum the output of RTO generation within each load zone: 𝑢𝑛𝑖𝑡=1 𝑅𝑇𝑂_𝐺𝑒𝑛𝑧𝑜𝑛𝑒 = ∑𝑎𝑙𝑙 𝐺𝑒𝑛𝑢𝑛𝑖𝑡,𝑧𝑜𝑛𝑒 , for each RTO load zone Where: zone = the relevant RTO load zone; unit = the relevant generator; RTO_Genzone = the sum of the RTO’s generation in a zone; and Genunit,zone = the real-time output of the unit in a given zone. Next, reduce the RTO generation located within a load zone by the scheduled line real-time export transaction schedules that source from that particular load zone: Where: 𝑅𝑇𝑂_𝑅𝑒𝑑𝑢𝑐𝑒𝑑_𝐺𝑒𝑛𝑧𝑜𝑛𝑒 = 𝑅𝑇𝑂_𝐺𝑒𝑛𝑧𝑜𝑛𝑒 − ∑ 𝐸𝑥𝑝𝑜𝑟𝑡_𝑆𝑐ℎ𝑒𝑑𝑢𝑙𝑒𝑠𝑠𝑐ℎ𝑒𝑑𝑢𝑙𝑒𝑑_𝑙𝑖𝑛𝑒,𝑧𝑜𝑛𝑒 zone = the relevant RTO load zone; scheduled_line = each of the Transmission Facilities identified in Table 1 above; RTO_Reduced_Genzone = the sum of the RTO’s generation in a zone reduced by the sum of export schedules over scheduled lines from the zone; RTO_Genzone = the sum of the RTO’s generation in a zone; and Export_Schedulesscheduled_line,zone = export schedules from a zone over a scheduled line. The real-time export schedules over scheduled lines will only reduce the generation in the source zones identified in Table 1 above. The resulting generator output based on this reduction is defined below. 𝑅𝑇𝑂_𝑅𝑒𝑑𝑢𝑐𝑒𝑑_𝐺𝑒𝑛𝑧𝑜𝑛𝑒 Where: 𝑅𝑒𝑑𝑢𝑐𝑒𝑑 𝐺𝑒𝑛𝑢𝑛𝑖𝑡 = 𝐺𝑒𝑛𝑢𝑛𝑖𝑡,𝑧𝑜𝑛𝑒 ( 𝑅𝑇𝑂_𝐺𝑒𝑛 ) 𝑧𝑜𝑛𝑒 unit = the relevant generator; zone = the relevant RTO load zone; Genunit,zone = the real-time output of the unit in a given zone; Reduced Genunit = each unit’s real-time output after reducing the RTO_Net_Gen by the real-time export schedules over scheduled lines; RTO_Reduced_Genzone = the sum of the RTO’s generation in a zone reduced by the sum of export schedules over scheduled lines from the zone; and RTO_Genzone = the sum of the RTO’s generation in a zone. Once export schedules over scheduled lines are accounted for, it is then appropriate to reduce the net RTO generation by the remaining real-time export schedules at the proxies identified in Table 2 above. Where: 𝑅𝑇𝑂_𝑁𝑒𝑡_𝐺𝑒𝑛 = ∑ 𝑅𝑇𝑂_𝑅𝑒𝑑𝑢𝑐𝑒𝑑_𝐺𝑒𝑛𝑧𝑜𝑛𝑒 zone = the relevant RTO load zone; RTO_Net_Gen = the sum of the RTO’s generation reduced by the sum of export schedules over all scheduled lines; and RTO_Reduced_Genzone = the sum of the RTO’s generation in a zone reduced by the sum of export schedules over scheduled lines from the z...
Compute RTO Generation Serving RTO Load. Using the real-time generation output in MWs, compute the Generation serving RTO Load. Sum the output of RTO generation within each load zone: 𝑅𝑇𝑂_𝐺𝑒𝑛𝑧𝑜𝑛𝑒 𝑎𝑙𝑙 = ∑ 𝑢𝑛𝑖𝑡=1 𝐺𝑒𝑛𝑢𝑛𝑖𝑡,𝑧𝑜𝑛𝑒, for each RTO load zone Where: zone = the relevant RTO load zone; unit = the relevant generator; RTO_Genzone = the sum of the RTO’s generation in a zone; and Genunit,zone = the real-time output of the unit in a given zone. Next, reduce the RTO generation located within a load zone by the scheduled line real-time export transaction schedules that source from that particular load zone: 𝑅𝑇𝑂_𝑅𝑒𝑑𝑢𝑐𝑒𝑑_𝐺𝑒𝑛𝑧𝑜𝑛𝑒 = 𝑅𝑇𝑂_𝐺𝑒𝑛𝑧𝑜𝑛𝑒 − � 𝐸𝑥𝑝𝑜𝑟𝑡_𝑆𝑐ℎ𝑒𝑑𝑢𝑙𝑒𝑠𝑠𝑐ℎ𝑒𝑑𝑢𝑙𝑒𝑑_𝑙𝑖𝑛𝑒,𝑧𝑜𝑛𝑒 𝑠𝑐ℎ𝑒𝑑𝑢𝑙𝑒𝑑_𝑙𝑖𝑛𝑒=1

Related to Compute RTO Generation Serving RTO Load

  • Synchronous Generation The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established different requirements that apply to all similarly situated generators in the New York Control Area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice.

  • Non-Synchronous Generation The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the high-side of the generator substation at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established a different power factor range that applies to all similarly situated non-synchronous generators in the control area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice. This power factor range standard shall be dynamic and can be met using, for example, power electronics designed to supply this level of reactive capability (taking into account any limitations due to voltage level, real power output, etc.) or fixed and switched capacitors, or a combination of the two. This requirement shall only apply to newly interconnecting non-synchronous generators that have not yet executed a Facilities Study Agreement as of September 21, 2016.

  • Scope of Interconnection Service 1.3.1 The NYISO will provide Energy Resource Interconnection Service and Capacity Resource Interconnection Service to Interconnection Customer at the Point of Interconnection. 1.3.2 This Agreement does not constitute an agreement to purchase or deliver the Interconnection Customer’s power. The purchase or delivery of power and other services that the Interconnection Customer may require will be covered under separate agreements, if any, or applicable provisions of NYISO’s or Connecting Transmission Owner’s tariffs. The Interconnection Customer will be responsible for separately making all necessary arrangements (including scheduling) for delivery of electricity in accordance with the applicable provisions of the ISO OATT and Connecting Transmission Owner’s tariff. The execution of this Agreement does not constitute a request for, nor agreement to, provide Energy, any Ancillary Services or Installed Capacity under the NYISO Services Tariff or any Connecting Transmission Owner’s tariff. If Interconnection Customer wishes to supply or purchase Energy, Installed Capacity or Ancillary Services, then Interconnection Customer will make application to do so in accordance with the NYISO Services Tariff or Connecting Transmission Owner’s tariff.

  • System Logging The system must maintain an automated audit trail which can 20 identify the user or system process which initiates a request for PHI COUNTY discloses to 21 CONTRACTOR or CONTRACTOR creates, receives, maintains, or transmits on behalf of COUNTY, 22 or which alters such PHI. The audit trail must be date and time stamped, must log both successful and 23 failed accesses, must be read only, and must be restricted to authorized users. If such PHI is stored in a 24 database, database logging functionality must be enabled. Audit trail data must be archived for at least 3 25 years after occurrence.

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!