Governor or Equivalent Controls. Whenever the Customer Facility is operated in parallel with the Transmission System, Generation Interconnection Customer shall operate the Customer Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved NERC
Appears in 25 contracts
Samples: Interconnection Service Agreement, Interconnection Service Agreement, Interconnection Service Agreement
Governor or Equivalent Controls. Whenever the Customer Generating Facility is operated in parallel with the Transmission System, Generation Interconnection Customer shall operate the Customer Generating Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1a) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2b) implement the relevant droop and deadband settings from an approved NERCNERC Reliability Standard that provides for equivalent or more stringent parameters. Interconnection Customer shall be required to provide the status and settings of the
Appears in 6 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Customer Generating Facility is operated in parallel with the Transmission System, Generation Interconnection Customer shall operate the Customer Generating Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1a) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved NERCparameter
Appears in 5 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Customer Generating Facility is operated in parallel with the Transmission System, Generation Interconnection Customer shall operate the Customer Generating Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1a) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2b) implement the relevant droop and deadband settings from an approved NERCNERC Reliability Standard that
Appears in 2 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Customer Generating Facility is operated in parallel with the Transmission System, Generation Interconnection Customer shall operate the Customer Generating Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1a) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2b) implement the relevant droop and deadband settings from an approved NERCNERC Reliability Standard that provides for equivalent or more stringent parameters. Interconnection
Appears in 2 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Customer Qualifying Facility is operated in parallel with the Transmission System, Generation Interconnection Customer shall operate the Customer Qualifying Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) , in coordination with Transmission Provider Company and/or the relevant balancing authority, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved NERCdroop
Appears in 1 contract
Samples: Qualifying Facility Transmission Interconnection Agreement
Governor or Equivalent Controls. Whenever the Customer Small Generating Facility is operated in parallel with the Transmission System, Generation Interconnection Customer shall operate the Customer Small Generating Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved NERCNERC Reliability Standard that
Appears in 1 contract
Governor or Equivalent Controls. Whenever the Customer Large Generating Facility is operated in parallel with the Transmission System, Generation Interconnection Customer shall operate the Customer Large Generating Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved NERCNERC Reliability Standard that provides for equivalent or more stringent parameters. Interconnection Customer
Appears in 1 contract
Samples: Standard Large Generator Interconnection Agreement (Lgia)