Governor or Equivalent Controls. Whenever the Generating Facility is operated in parallel with the Transmission System, Interconnection Customer shall operate the Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (a) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b) implement the relevant droop and deadband settings from an approved NERC Reliability Standard that
Appears in 2 contracts
Samples: Interconnection Agreement, Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Large Generating Facility is operated in parallel with the New England Transmission System, Interconnection Customer shall operate the Large Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) in coordination with System Operator and Interconnecting Transmission Provider and/or the relevant balancing authorityOwner, set the deadband parameter to: (a1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b2) implement the relevant droop and deadband settings from an approved NERC Reliability Standard thatthat provides for equivalent or more stringent parameters.
Appears in 2 contracts
Samples: Large Generator Interconnection Agreement, Large Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Large Generating Facility is operated in parallel with the New England Transmission System, Interconnection Customer shall operate the Large Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) in coordination with System Operator and Interconnecting Transmission Provider and/or the relevant balancing authorityOwner, set the deadband parameter to: (a1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b2) implement the relevant droop and deadband settings from an approved NERC Reliability Standard thatReliability
Appears in 2 contracts
Samples: Electronic Filing, Large Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Generating Facility is operated in parallel with the Transmission System, Interconnection Customer shall operate the Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) ), in coordination with Transmission Provider and/or the relevant balancing authorityProvider, set the deadband parameter to: (a1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b) implement the relevant droop and deadband settings from an approved NERC Reliability Standard thator
Appears in 1 contract
Samples: Interconnection Agreement
Governor or Equivalent Controls. Whenever the Generating Facility is operated in parallel with the Transmission System, Interconnection Customer shall operate the Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (a) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b) implement the relevant droop and deadband settings from an approved NERC Reliability Standard thatthat provides for equivalent or more stringent parameters. Interconnection
Appears in 1 contract
Samples: Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Large Generating Facility is operated in parallel with the New York State Transmission System, Interconnection Customer CustomerDeveloper shall operate the Large Generating Facility with its governor or equivalent controls in service and responsive to frequency. Developer Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authorityNYISO, set the deadband parameter to: (a1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b2) implement the relevant droop and deadband settings from an approved NERC Applicable Reliability Standard thatRequirementsStandard that provides for equivalent or more stringent parameters.
Appears in 1 contract
Samples: Yearcluster Study Agreement
Governor or Equivalent Controls. Whenever the Generating Facility is operated in parallel with the Transmission System, Interconnection Customer shall operate the Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) ), in coordination with Transmission Provider and/or the relevant balancing authorityProvider, set the deadband parameter to: (a1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b2) implement the relevant droop and deadband settings from an approved NERC Applicable Reliability Standard thatthat provides for equivalent or more stringent parameters.
Appears in 1 contract
Samples: Interconnection Agreement
Governor or Equivalent Controls. Whenever the Large Generating Facility is operated in parallel with the Transmission System, Interconnection Customer shall operate the Large Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (a1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b2) implement the relevant droop and deadband settings from an approved NERC Reliability Standard thatthat provides for equivalent or more stringent parameters. Interconnection Customer
Appears in 1 contract