Governor or Equivalent Controls. Whenever the Small Generating Facility is operated in parallel with the New York State Transmission System, Interconnection Customer shall operate the Small Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) in coordination with NYISO, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved Applicable Reliability Standard that provides for equivalent or more stringent parameters. Interconnection Customer shall be required to provide the status and settings of the governor and equivalent controls to NYISO and/or the Connecting Transmission Owner upon request. If Interconnection Customer needs to operate the Small Generating Facility with its governor or equivalent controls not in service, Interconnection Customer shall immediately notify NYISO and the Connecting Transmission Owner, and provide both with the following information: (1) the operating status of the governor or equivalent controls (i.e., whether it is currently out of service or when it will be taken out of service); (2) the reasons for removing the governor or equivalent controls from service; and (3) a reasonable estimate of when the governor or equivalent controls will be returned to service. Interconnection Customer shall make Reasonable Efforts to return its governor or equivalent controls into service as soon as practicable. Interconnection Customer shall make Reasonable Efforts to keep outages of the Small Generating Facility’s governor or equivalent controls to a minimum whenever the Small Generating Facility is operated in parallel with the New York State Transmission System.
Appears in 4 contracts
Samples: Standard Small Generator Interconnection Agreement, Interconnection Agreement, Standard Small Generator Interconnection Agreement (Sgia)
Governor or Equivalent Controls. Whenever the Small Generating Facility is operated in parallel with the New York State Transmission System, Interconnection Customer shall operate the Small Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) in coordination with NYISO, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved Applicable Reliability Standard that provides for equivalent or more stringent parameters. Interconnection Customer shall be required to provide the status and settings of the governor and equivalent controls to NYISO and/or the Connecting Transmission Owner upon request. If Interconnection Customer needs to operate the Small Generating Facility with its governor or equivalent controls not in service, Interconnection Customer shall immediately notify NYISO and the andthe Connecting Transmission Owner, and provide both with the following information:
(1) the operating status of the governor or equivalent controls (i.e., whether it is currently out of service or when it will be taken out of service);
(2) the reasons thereasons for removing the governor or equivalent controls from service; and
(3) a reasonable estimate of when the governor or equivalent controls will be returned to service. Interconnection Customer shall make Reasonable Efforts to return its governor or equivalent controls into service as soon as practicable. Interconnection Customer shall make Reasonable Efforts to keep outages of the Small Generating Facility’s governor or equivalent controls to a minimum whenever the Small Generating Facility is operated in parallel with the New York State YorkState Transmission System.
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
Governor or Equivalent Controls. Whenever the Small Electric Generating Facility Unit(s) is operated in parallel with the New York State Transmission SystemCAISO Controlled Grid, Interconnection Customer shall operate the Small Electric Generating Facility Unit(s) with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) , in coordination with NYISOthe CAISO, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved Applicable Reliability Standard Standards that provides for equivalent or more stringent parameters. Interconnection Customer shall be required to provide the status and settings of the governor and or equivalent controls to NYISO and/or the Connecting Transmission Owner CAISO upon request. If Interconnection Customer needs to operate the Small Electric Generating Facility Unit(s) with its governor or equivalent controls not in service, Interconnection Customer shall immediately notify NYISO and the Connecting Transmission OwnerCAISO, and provide both with the following information:
: (1) the operating status of the governor or equivalent controls (i.e., whether it is currently out of service or when it will be taken out of service);
; (2) the reasons for removing the governor or equivalent controls from service; and
and (3) a reasonable estimate of when the governor or equivalent controls will be returned to service. Interconnection Customer shall make Reasonable Efforts to return its governor or equivalent controls into service as soon as practicable. Interconnection Customer shall make Reasonable Efforts to keep outages of the Small Electric Generating Facility’s Units’ governor or equivalent controls to a minimum whenever the Small Electric Generating Facility Unit(s) is operated in parallel with the New York State Transmission SystemCAISO Controlled Grid.
Appears in 2 contracts
Samples: Large Generator Interconnection Agreement, Large Generator Interconnection Agreement
Governor or Equivalent Controls. Whenever the Small Electric Generating Facility Unit(s) is operated in parallel with the New York State Transmission SystemCAISO Controlled Grid, Interconnection Customer shall operate the Small Electric Generating Facility Unit(s) with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) , in coordination with NYISOthe CAISO, set the deadband parameter to: :
(1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved Applicable Reliability Standard Standards that provides for equivalent or more stringent parameters. Interconnection Customer shall be required to provide the status and settings of the governor and or equivalent controls to NYISO and/or the Connecting Transmission Owner CAISO upon request. If Interconnection Customer needs to operate the Small Electric Generating Facility Unit(s) with its governor or equivalent controls not in service, Interconnection Customer shall immediately notify NYISO and the Connecting Transmission OwnerCAISO, and provide both with the following information:
: (1) the operating status of the governor or equivalent controls (i.e., whether it is currently out of service or when it will be taken out of service);
(2) the reasons for removing the governor or equivalent controls from service; and
(3) a reasonable estimate of when the governor or equivalent controls will be returned to service. Interconnection Customer shall make Reasonable Efforts to return its governor or equivalent controls into service as soon as practicable. Interconnection Customer shall make Reasonable Efforts to keep outages of the Small Electric Generating Facility’s Units’ governor or equivalent controls to a minimum whenever the Small Electric Generating Facility Unit(s) is operated in parallel with the New York State Transmission SystemCAISO Controlled Grid.
Appears in 1 contract
Governor or Equivalent Controls. Whenever the Small Large Generating Facility is operated in parallel with the New York State Transmission System, Interconnection Customer Developer shall operate the Small Large Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer Developer shall: (1) in coordination with NYISO, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings SERVICE AGREEMENT NO. 2629 from an approved Applicable Reliability Standard that provides for equivalent or more stringent parameters. Interconnection Customer Developer shall be required to provide the status and settings of the governor and equivalent controls to NYISO and/or the Connecting Transmission Owner upon request. If Interconnection Customer Developer needs to operate the Small Large Generating Facility with its governor or equivalent controls not in service, Interconnection Customer Developer shall immediately notify NYISO and the Connecting Transmission Owner, and provide both with the following information:
: (1) the operating status of the governor or equivalent controls (i.e., whether it is currently out of service or when it will be taken out of service);
; (2) the reasons for removing the governor or equivalent controls from service; and
and (3) a reasonable estimate of when the governor or equivalent controls will be returned to service. Interconnection Customer Developer shall make Reasonable Efforts to return its governor or equivalent controls into service as soon as practicable. Interconnection Customer Developer shall make Reasonable Efforts to keep outages of the Small Large Generating Facility’s governor or equivalent controls to a minimum whenever the Small Large Generating Facility is operated in parallel with the New York State Transmission System.
Appears in 1 contract
Governor or Equivalent Controls. Whenever the Small Generating Customer Facility is operated in parallel with the New York State Transmission System, Generation Interconnection Customer shall operate the Small Generating Customer Facility with its governor or equivalent controls in service and responsive to frequency. Generation Interconnection Customer shall: (1) in coordination with NYISOTransmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved Applicable NERC Reliability Standard that provides for equivalent or more stringent parameters. Generation Interconnection Customer shall be required to provide the status and settings of the governor and or equivalent controls to NYISO Transmission Provider and/or the Connecting Transmission Owner relevant balancing authority upon request. If Generation Interconnection Customer needs to operate the Small Generating Customer Facility with its governor or equivalent controls not in service, Generation Interconnection Customer shall immediately notify NYISO Transmission Provider and the Connecting Transmission Ownerrelevant balancing authority, and provide both with the following information:
: (1) the operating status of the governor or equivalent controls (i.e., whether it is currently out of service or when it will be taken out of service);
; (2) the reasons for removing the governor or equivalent controls from service; and
and (3) a reasonable estimate of when the governor or equivalent controls will be returned to service. Generation Interconnection Customer shall make Reasonable Efforts to return its governor or equivalent controls into service as soon as practicable. Generation Interconnection Customer shall make Reasonable Efforts to keep outages of the Small Generating Customer Facility’s governor or equivalent controls to a minimum whenever the Small Generating Customer Facility is operated in parallel with the New York State Transmission System.
Appears in 1 contract
Samples: Interconnection Service Agreement
Governor or Equivalent Controls. Whenever the Small Generating Facility is operated in parallel with the New York State Transmission System, Interconnection Customer shall operate the Small Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer shall: (1) in coordination with NYISO, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved Applicable Reliability Standard that provides for equivalent or more stringent parameters. Interconnection Customer shall be required to provide the status and settings of the governor and equivalent controls to NYISO and/or the Connecting Transmission Owner upon request. If Interconnection Customer needs to operate the Small Generating Facility with its governor or equivalent controls not in service, Interconnection Customer shall immediately notify NYISO and the andthe Connecting Transmission Owner, and provide both with the following information:
(1) the operating status of the governor or equivalent controls (i.e., whether it is currently out of service or when it will be taken out of service);
(2) the reasons thereasons for removing the governor or equivalent controls from service; and
(3) a reasonable estimate of when the governor or equivalent controls will be returned to servicetoservice. Interconnection Customer shall make Reasonable Efforts to return its governor or equivalent controls into service as soon as practicable. Interconnection Customer shall make Reasonable Efforts to keep outages of the Small Generating Facility’s governor or equivalent controls to a minimum whenever the Small Generating Facility is operated in parallel with the New York State YorkState Transmission System.
Appears in 1 contract
Samples: Service Agreement
Governor or Equivalent Controls. Whenever the Small Generating Facility is operated in parallel with the New York State Transmission System, Interconnection Customer Generation Project Developer shall operate the Small Generating Facility with its governor or equivalent controls in service and responsive to frequency. Interconnection Customer Generation Project Developer shall: :
(1) in coordination with NYISOTransmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent5%; or (2) implement the relevant droop and deadband settings from an approved Applicable NERC Reliability Standard that provides for equivalent or more stringent parameters. Interconnection Customer Generation Project Developer shall be required to provide the status and settings of the governor and or equivalent controls to NYISO Transmission Provider and/or the Connecting Transmission Owner relevant balancing authority upon request. If Interconnection Customer Generation Project Developer needs to operate the Small Generating Facility with its governor or equivalent controls not in service, Interconnection Customer Generation Project Developer shall immediately notify NYISO Transmission Provider and the Connecting Transmission Ownerrelevant balancing authority, and provide both with the following information:
: (1) the operating status of the governor or equivalent controls (i.e., whether it is currently out of service or when it will be taken out of service);
(2) the reasons for removing the governor or equivalent controls from service; and
(3) a reasonable estimate of when the governor or equivalent controls will be returned to service. Interconnection Customer Generation Project Developer shall make Reasonable Efforts to return its governor or equivalent controls into service as soon as practicable. Interconnection Customer Generation Project Developer shall make Reasonable Efforts to keep outages of the Small Generating Facility’s governor or equivalent controls to a minimum whenever the Small Generating Facility is operated in parallel with the New York State Transmission System.
Appears in 1 contract
Samples: Execution Deadlines