Grounding System Sample Clauses

Grounding System i) All ground connections shall be checked and the entire system shall be checked for continuity. The resistance of the ground system at each site shall be measured using a 3-point fall-of-potential method. The maximum ground resistance shall be three ohms.
AutoNDA by SimpleDocs
Grounding System. Inspect grounding system connections for mechanical and electrical integrity, corrosion, and damage. Spot check torques.
Grounding System. Perform electrical resistance testing to verify continuity of grounding systems. Measure current on ground cables and test for ground faults.
Grounding System. 8.3. A The Contractor shall re-connect all necessary equipment and hardware to the grounding system and install new grounding connections as indicated by the Contract Standards and drawings or any requirements of the Contract.
Grounding System. A grounding system should be provided to discharge static charges accumulated in the DCP structure and provide a stable voltage reference for the equipment, following the standards NBRs 13.571/96, 5426/85, 5456/87, 6006/80, ASTM E 478, UL-467, or other standards ensuring equal or superior quality. The grounding system planned should have the following minimum characteristics:
Grounding System. CROWN will install a buried Site ring in accordance with Ericsson standards (to be provided by TRITON to CROWN)and provide a coiled length of ground wire to connect to TRITON's BTS equipment. CROWN will install all other required external grounding. Ground ring connections will be cadwelded except the connection to the master ground bar and all coax grounding kit connections will be mechanical. Notwithstanding the foregoing, all grounding shall meet or exceed Ericsson grounding requirements identified in Exhibit "I-I-B-i".
Grounding System a. A site survey shall be performed to determine the grounding grid design for the station.
AutoNDA by SimpleDocs
Grounding System i. Replace two defective exothermic weld connections. (completed prior to 8/17/04)
Grounding System o.1) New substations must have a deep grounding grid securing personnel against contact voltages. At the same time, the grounding grid should allow the safe discharge to land of lightning over-voltages without the equipment installed being affected.

Related to Grounding System

  • Monitoring System In each case in which the Custodian has exercised delegated authority to place Assets with a Foreign Custodian, the Custodian shall establish a system, to re-assess or re-evaluate selected Foreign Custodians, at least annually in accordance with Rule 17f-5(c)(3).

  • Roof Any leaks or evidence of moisture? Yes No Unknown Type of Roof: Age Comments: Is there any existing fire retardant treated plywood? Yes No Unknown Comments:

  • HVAC A. Heating, ventilating and air conditioning equipment will be provided with sufficient capacity to accommodate a maximum population density of one (1) person per one hundred fifty (150) square feet of useable floor area served, and a combined lighting and standard electrical load of 3.0 xxxxx per square foot of useable floor area. In the event Tenant introduces into the Premises personnel or equipment which overloads the system’s ability to adequately perform its proper functions, Landlord shall so notify Tenant in writing and supplementary system(s) may be required and installed by Landlord at Tenant’s expense, if within fifteen (15) days Tenant has not modified its use so as not to cause such overload. Operating criteria of the basic system shall not be less than the following:

  • Hardware and Software Requirements In order to access and retain Disclosures electronically, you must satisfy the following computer hardware and software requirements: access to the Internet; an email account and related software capable of receiving email through the Internet; a web browser which is SSL-compliant and supports secure sessions, and hardware capable of running this software.

  • Compatibility 1. Any unresolved issue arising from a mutual agreement procedure case otherwise within the scope of the arbitration process provided for in this Article and Articles 25A to 25G shall not be submitted to arbitration if the issue falls within the scope of a case with respect to which an arbitration panel or similar body has previously been set up in accordance with a bilateral or multilateral convention that provides for mandatory binding arbitration of unresolved issues arising from a mutual agreement procedure case.

  • Floor Loading Floor loading capacity shall be within building design capacity. Tenant may exceed floor loading capacity with Landlord’s consent, at Landlord’s sole discretion and must, at Tenant’s sole cost and expense, reinforce the floor as required for such excess loading.

  • Configuration The configuration for the Purchase Right Aircraft will be the Detail Specification for Model 767-3S2F aircraft at the revision level in effect at the time of the Supplemental Agreement. Such Detail Specification will be revised to include (i) changes required to obtain required regulatory certificates and (ii) other changes as mutually agreed upon by Boeing and Customer.

Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!