Common use of Meter Test Checking Clause in Contracts

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by Corporation at its own cost and expense and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% accuracy class. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter and the corresponding check meter are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 % accuracy class, all the meters shall be re-tested and calibrated immediately.

Appears in 4 contracts

Samples: Power Purchase Agreement, Power Purchase Agreement, Power Purchase Agreement

AutoNDA by SimpleDocs

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter owned by the ESCOM which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by Corporation at its own cost and expense and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% 0.2 accuracy class. The cost of such test checking shall be borne by the Company at the rates specified by the ESCOM from time to time. The consumption registered by the main meters alone will hold good shall be considered for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit limits of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the readings of the main meter as usualmeter. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be show any reading beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will shall be a revision in the bills for the period from the previous calibration test upto billing date up to the current test date, based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter and the corresponding check meter are found to be show readings beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction corrections applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto up to the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 % accuracy class, all the meters shall be re-tested and calibrated for their accuracy immediately.

Appears in 3 contracts

Samples: Wheeling and Banking Agreement, Wheeling and Banking Agreement, Wheeling and Banking Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by Corporation ESCOM at its own cost and expense and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% 0.2 accuracy class. The cost of such test checking shall be borne by the Company at the rates specified by ESCOM from time to time. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit limits of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the readings of the main meter as usualmeter. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be show any reading beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will shall be a revision in the bills for the period from the previous calibration test upto billing date up to the current test date, based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter and the corresponding check meter are found to be show readings beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction corrections applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto up to the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 % 0.2s accuracy class, all the meters shall be re-tested and calibrated for their accuracy immediately.

Appears in 2 contracts

Samples: Wheeling Agreement, Wheeling Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by Corporation ESCOM at its own cost and expense and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% 0.2 accuracy class. The cost of such test checking shall be borne by the Company at the rates specified by ESCOM from time to time. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto billing date up to the current test date, based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter and the corresponding check meter are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto up to the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 % accuracy class, all the meters shall be re-tested and calibrated for its accuracy immediately.

Appears in 1 contract

Samples: Wheeling and Banking Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%0.1 Class. The portable standard meter shall be owned by Corporation the Distribution utility at its own cost and expense and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% 0.2 accuracy class. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto up to the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter meters and the corresponding check meter meters are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto up to the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 % accuracy classClass accuracy, all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement (Ppa)

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of have an accuracy class of 0.1%. 0.1S. The portable standard meter shall be owned by Corporation ...ESCOM at its own cost and expense and and, tested and certified at least once every year against an accepted laboratory standard Standard meter in accordance with electricity standardsthe Electricity Standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters having accuracy class of 0.2% accuracy class. 0.2S. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto up to the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter meters and the corresponding check meter meters are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction shall be applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters having accuracy class of 0.2 % accuracy class0.2S, all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by Corporation ..Escom at its own cost and expense expenses and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity the Electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% accuracy class. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter meters and the corresponding check meter meters are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 0.2% accuracy class, all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by Corporation at its own cost and expense expenses and tested and certified at least atleast once every year against an accepted laboratory standard meter in accordance with electricity the Electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% accuracy class. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter meters and the corresponding check meter meters are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 0.2% accuracy class, all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by the Corporation at its own cost and expense and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% accuracy class. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter meters and the corresponding check meter meters are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 % accuracy class, all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement

AutoNDA by SimpleDocs

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by Corporation the ..ESCOM at its own cost and expense and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% accuracy class. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto up to the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter meters and the corresponding check meter meters are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto up to the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 % accuracy class, all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of an accuracy class of 0.1%. The portable standard meter shall be owned by Corporation ESCOM /CESC at its own cost and expense and tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters of 0.2% 0.2 accuracy class. The cost of such test checking shall be borne by the Company at the rates specified by the Corporation/ESCOM/s/CESC from time to time. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit limits of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the readings of the main meter as usualmeter. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be show any reading beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will shall be a revision in the bills for the period from the previous calibration test upto billing date up to the current test date, based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter and the corresponding check meter are found to be show readings beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction corrections applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto up to the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters of 0.2 % 0.2s accuracy class, all the meters shall be re-tested and calibrated for their accuracy immediately.

Appears in 1 contract

Samples: Wheeling Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of have an accuracy class of 0.1%. 0.1S. The portable standard meter shall be owned by Corporation at its own cost and expense and and, tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standardsElectricity Standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters having accuracy class of 0.2% accuracy class. 0.2S. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto up to the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter and the corresponding check meter are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction shall be applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters having accuracy class of 0.2 % accuracy class0.2S, all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of have an accuracy class of 0.1%. 0.1S. The portable standard meter shall be owned by Corporation at its own cost and expense and and, tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standardsElectricity Standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters having accuracy class of 0.2% accuracy class. 0.2S. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto up to the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter and the corresponding check meter are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction shall be applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto up to the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters having accuracy class of 0.2 % accuracy class0.2S, all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement

Meter Test Checking. All the main and check meters shall be tested for accuracy every calendar quarter with reference to a portable standard meter which shall be of have an accuracy class of 0.1%. 0.1S. The portable standard meter shall be owned by Corporation the ...ESCOM at its own cost and expense and and, tested and certified at least once every year against an accepted laboratory standard meter in accordance with electricity standardsElectricity Standards. The meters shall be deemed to be working satisfactorily if the errors are within specifications for meters having accuracy class of 0.2% accuracy class. 0.2S. The consumption registered by the main meters alone will hold good for the purpose of billing as long as the error in the main meter is within the permissible limits. (i) If during the quarterly tests, the main meter is found to be within the permissible limit of error and the corresponding check meter is beyond the permissible limits, then billing will be as per the main meter as usual. The check meter shall, however, be calibrated immediately. (ii) If during the quarterly tests, the main meter is found to be beyond permissible limits of error, but the corresponding check meter is found to be within permissible limits of error, then the billing for the month upto up to the date and time of such test shall be as per the check meter. There will be a revision in the bills for the period from the previous calibration test upto up to the current test based on the readings of the check meter. The main meter shall be calibrated immediately and billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter. (iii) If during the quarterly tests, both the main meter meters and the corresponding check meter meters are found to be beyond the permissible limits of error, both the meters shall be immediately calibrated and the correction shall be applied to the reading registered by the main meter to arrive at the correct reading of energy supplied for billing purposes for the period from the last month's meter reading upto the current test. Billing for the period thereafter till the next monthly meter reading shall be as per the calibrated main meter.by (iv) If during any of the monthly meter readings, the variation between the main meter and the check meter is more than that permissible for meters having accuracy class of 0.2 % accuracy class0.2S , all the meters shall be re-tested and calibrated immediately.

Appears in 1 contract

Samples: Power Purchase Agreement