New Line Position. The new line position required to interconnect the Small Generating Facility will require installation of: (1) steel bus support structure and associated caisson foundations; (1) steel switch structure with associated caisson foundation; (1) steel cable riser/switch structure with caisson foundation; • One (1) 46kV, 350kV BIL, 2000A, 31.5kA vacuum circuit breaker (R215) and foundation; • Three (3) in-line 900A transmission disconnect switches, to be normally open (SW212); and • Two (2) gang-operated 2000A switches (SW218, SW219). The ground grid will be expanded to meet the new fence line, and the new breaker and steel structures will be grounded to the existing ground grid.