Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety. 13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity. 13.3 That the use of any PVC material is not permitted in the underground stations. 13.4 Applicant will also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s approval). 13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max connected load up to 10 KW, Electrical load requirement exceeding 10 KW will be given on 3-phase, 415V, 50Hz subject to availability. 13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS. 13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load. 13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load only. 13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case. 13.10 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant.
Appears in 6 contracts
Samples: License Agreement, License Agreement for Exclusive Advertising Rights, License Agreement for Exclusive Semi Naming Rights
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables Licensee shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantBidder. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Bidder or at a common meter room/board. Applicant Bidder shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicantBidder. Approval to the layouts/ schemes/ layouts/schemes/details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use Only FRLS cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Licensee premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will Licensee shall also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant Licensee shall use FRZHLS FRLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will Licensee shall have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant Licensee shall use Energy efficient lighting lighting& shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant Licensee shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Licensee’s cost shall carry the entire work. DMRC’s representative may inspect and supervise the work.
13.11 Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant Bidder shall be submitted by the ApplicantLicensee. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Licensee shall not be allowed to provide Room Heating appliance of any kind.
13.13 The power shall be supplied normally at the rate of 0.5 KVA/Xx.Xxx. of space licensed out. Minimum load to be given shall be 2 KVA on which the demand charges as applicable shall be paid by the Licensee. Additional power up to 10 kW on single phase and thereafter on three phase system if required by the Licensee shall be supplied subject to availability at an additional cost and conditions to be stipulated by DMRC.
13.14 In case, Licensee draws power more than the connected load, his electricity connection shall be disconnected. The electricity connection shall be provided back on first occasion only when Licensee pays necessary penalty as per State ERC norms and removes excess load. On the subsequent occasion, DMRC reserves the right to revoke the license and forfeit the interest free security deposit after adjustment of all dues what so ever.
13.15 In case, the Licensee is found misusing Electricity or tampering with the Energy meter, a token penalty of Rs. 1000/- shall be charged from him along with disconnection of power supply. Reconnection of power supply shall be done only after charging Rs. 100/- as reconnection fee and clearance of all dues duly obtaining approval of Competent Authority of DMRC.
Appears in 4 contracts
Samples: License Agreement, License Agreement, License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor FRLS/ LSZH (as applicable) cables shall be used. Applicant will Licensee shall have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantBidder. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Bidder or at a common meter room/boardboard (Common meter room is locked & key, access is not permitted to licensee). Applicant Bidder shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicantBidder. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant Licensee hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant will Licensee shall also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant Licensee shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will Licensee shall have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant Licensee shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant Bidder shall be submitted by the ApplicantLicensee.
Appears in 4 contracts
Samples: License Agreement, License Agreement, License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will Licensee shall have to provide a Low voltage switch-switch- board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantBidder. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Bidder or at a common meter room/board. Applicant Bidder shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicantBidder. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant Licensee hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant will Licensee shall also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant Licensee shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will Licensee shall have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant Licensee shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant Bidder shall be submitted by the ApplicantLicensee.
Appears in 4 contracts
Samples: License Agreement, License Agreement, License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables Licensee shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantBidder. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Bidder or at a common meter room/board. Applicant Bidder shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safetysafety (if installed within his premises).
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricityBidder.
13.3 That the use Only FRLS/FRLSZH (as applicable) cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Licensee premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will Licensee shall also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant Licensee shall use FRZHLS copper FRLS/FRLSZH copper/aluminum wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load Load& Total Connected load shall be treated as same. Applicant will Licensee shall have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant Licensee shall use Energy efficient lighting lighting& shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant Licensee shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Licensee’s cost shall carry the entire work. DMRC’s representative may inspect and supervise the work.
13.11 Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant Bidder shall be submitted by the ApplicantLicensee. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Licensee shall not be allowed to provide Room Heating appliance of any kind.
13.13 The power shall be supplied normally at the rate of 0.5 KVA/Xx.Xxx. of space licensed out. Minimum load to be given shall be 2 KVA on which the demand charges as applicable shall be paid by the Licensee. Additional power up to 10 kW on single phase and thereafter on three phase system if required by the Licensee shall be supplied subject to availability at an additional cost and conditions to be stipulated by DMRC.
13.14 In case, Licensee draws power more than the connected load, his electricity connection shall be disconnected. The electricity connection shall be provided back on first occasion only when Licensee pays necessary penalty as per State ERC norms and removes excess load. On the subsequent occasion, DMRC reserves the right to revoke the license and forfeit the interest free security deposit after adjustment of all dues what so ever.
13.15 In case, the Licensee is found misusing Electricity or tampering with the Energy meter, suitable action shall be taken to respective State Electricity Act.
Appears in 4 contracts
Samples: License Agreement, License Agreement, License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ layouts/schemes/details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use Only FRLS cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Applicant premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant shall use FRZHLS FRLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load Load& Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than that 100 Lux in any case.
13.10 Applicant shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Applicant’s cost shall carry the entire work. DMRC’s representative may inspect and supervise the work.
13.11 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the ApplicantApplicant . Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Applicant will not be allowed to provide Room Heating appliance of any kind.
Appears in 3 contracts
Samples: License Agreement for Exclusive Advertising Rights, License Agreement, License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ layouts/schemes/details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use Only FRLS cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Applicant premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant shall use FRZHLS FRLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max connected max. Connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load Load& Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Applicant’s cost shall carry the entire work. DMRC’s representative may inspect and supervise the work.
13.11 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Applicant will not be allowed to provide Room Heating appliance of any kind.
13.13 The power shall be supplied normally at the rate of 0.5 KVA/Xx.Xxx. of space licensed out. Minimum load to be given shall be 2 KVA on which the demand charges as applicable shall be paid by the Applicant. Additional power up to 10 kW on single phase and thereafter on three phase system if required by the Applicant will be supplied subject to availability at an additional cost and conditions to be stipulated by DMRC.
13.14 In case, Applicant draws power more than the connected load, his electricity connection shall be disconnected. The electricity connection will be provided back on first occasion only when Applicant pays necessary penalty as per State ERC norms and removes excess load. On the subsequent occasion, DMRC reserves the right to revoke the license and forfeit the interest free security deposit.
13.15 In case, the Applicant is found misusing Electricity or tampering with the Energy meter, a token penalty of Rs. 1000/- will be charged from him along with disconnection of power supply. Reconnection of power supply will be done only after charging Rs. 100/- as reconnection fee and clearance of all dues duly obtaining approval of Competent Authority of DMRC.
Appears in 2 contracts
Samples: License Agreement, License Agreement for Exclusive Semi Naming Rights
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‟s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ layouts/schemes/details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use Only FRLS cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Applicant premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant shall use FRZHLS FRLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s DMRC‟s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max connected max. Connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will be given on 3-3- phase, 415V, 50Hz subject to availability.
13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load Load& Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Applicant‟s cost shall carry the entire work. DMRC‟s representative may inspect and supervise the work.
13.11 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s DMRC‟s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Applicant will not be allowed to provide Room Heating appliance of any kind.
13.13 The power shall be supplied normally at the rate of 0.5 KVA/Xx.Xxx. of space licensed out. Minimum load to be given shall be 2 KVA on which the demand charges as applicable shall be paid by the Applicant. Additional power up to 10 kW on single phase and thereafter on three phase system if required by the Applicant will be supplied subject to availability at an additional cost and conditions to be stipulated by DMRC.
13.14 In case, Applicant draws power more than the connected load, his electricity connection shall be disconnected. The electricity connection will be provided back on first occasion only when Applicant pays necessary penalty as per State ERC norms and removes excess load. On the subsequent occasion, DMRC reserves the right to revoke the license and forfeit the interest free security deposit.
13.15 In case, the Applicant is found misusing Electricity or tampering with the Energy meter, a token penalty of Rs. 1000/- will be charged from him along with disconnection of power supply. Reconnection of power supply will be done only after charging Rs. 100/- as reconnection fee and clearance of all dues duly obtaining approval of Competent Authority of DMRC.
Appears in 2 contracts
Samples: License Agreement, License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ layouts/schemes/details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use Only FRLS cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Applicant premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant shall use FRZHLS FRLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max connected max. Connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will be given on 3-3- phase, 415V, 50Hz subject to availability.
13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load Load& Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Applicant’s cost shall carry the entire work. DMRC’s representative may inspect and supervise the work.
13.11 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Applicant will not be allowed to provide Room Heating appliance of any kind.
13.13 The power shall be supplied normally at the rate of 0.5 KVA/Xx.Xxx. of space licensed out. Minimum load to be given shall be 2 KVA on which the demand charges as applicable shall be paid by the Applicant. Additional power up to 10 kW on single phase and thereafter on three phase system if required by the Applicant will be supplied subject to availability at an additional cost and conditions to be stipulated by DMRC.
13.14 In case, Applicant draws power more than the connected load, his electricity connection shall be disconnected. The electricity connection will be provided back on first occasion only when Applicant pays necessary penalty as per State ERC norms and removes excess load. On the subsequent occasion, DMRC reserves the right to revoke the license and forfeit the interest free security deposit.
13.15 In case, the Applicant is found misusing Electricity or tampering with the Energy meter, a token penalty of Rs. 1000/- will be charged from him along with disconnection of power supply. Reconnection of power supply will be done only after charging Rs. 100/- as reconnection fee and clearance of all dues duly obtaining approval of Competent Authority of DMRC.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor FRLS/ LSZH (as applicable) cables shall be used. Applicant will Licensee shall have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‘s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantBidder. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Bidder or at a common meter room/boardboard (Common meter room is locked & key, access is not permitted to licensee). Applicant Bidder shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicantBidder. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant Licensee hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant will Licensee shall also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant Licensee shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s DMRC‘s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant 14.1 Licensee will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his their cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 14.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his their premises shall be done by the applicantapplicant in line with scope of work provided by DMRC. Approval to the layouts/ schemes/ layouts/schemes/details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use 14.3 Only FRLS /FRLSZH cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Licensee premises in the underground stationsrigid GI Conduit pipe in line with specifications of Electrical works provided to applicant by DMRC.
13.4 Applicant 14.4 Licensee will also do wiring within his their shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/capping. The Applicant Licensee shall use FRZHLS FRLS /FRLSZH copper wire of the required size in line with specifications of Electrical works provided to applicant by DMRC (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 14.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max maximum connected load up to 10 KW, 10KW in line with specifications of Electrical works provided to applicant by DMRC. Electrical load requirement exceeding 10 KW above will be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant 14.6 Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his their requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant 14.7 Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant Licensee will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 14.8 The Total Demand Load Load& Total Connected load shall be treated as same. Applicant Licensee will have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant 14.9 Licensee shall use Energy efficient lighting lighting& shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux lux in any case.
13.10 Applicant 14.10 Licensee shall use Brand/make Electrical wiring and switch gear items in line with specifications of Electrical works provided to applicant by DMRC. The Electrical Contractor/agency at Licensee’s cost shall carry the entire work. DMRC’s representative may inspect and supervise the work.
14.11 Licensee shall provide proper Earthing earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the ApplicantLicensee. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
14.12 Licensee will not be allowed to provide Room Heating appliance of any kind.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 14.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant Licensee will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 14.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant licensee hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 14.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant 14.4 Licensee will also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant Licensee shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s approval).
13.5 14.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW, Electrical load requirement exceeding 10 KW will be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant 14.6 Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant 14.7 Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant Licensee will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 14.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant Licensee will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant 14.9 Licensee shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant 14.10 Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the ApplicantLicensee.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables Licensee shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantApplicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safetysafety (if installed within his premises).
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricityApplicant.
13.3 That the use Only FRLS/FRLSZH (as applicable) cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Licensee premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will Licensee shall also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant Licensee shall use FRZHLS copper FRLS/FRLSZH copper/aluminum wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load Load& Total Connected load shall be treated as same. Applicant will Licensee shall have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant Licensee shall use Energy efficient lighting lighting& shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant Licensee shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Licensee’s cost shall carry the entire work. DMRC’s representative may inspect and supervise the work.
13.11 Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant Applicant shall be submitted by the ApplicantLicensee. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Licensee shall not be allowed to provide Room Heating appliance of any kind.
13.13 The power shall be supplied normally at the rate of 0.5 KVA/Xx.Xxx. of space licensed out. Minimum load to be given shall be 2 KVA on which the demand charges as applicable shall be paid by the Licensee. Additional power up to 10 kW on single phase and thereafter on three phase system if required by the Licensee shall be supplied subject to availability at an additional cost and conditions to be stipulated by DMRC.
13.14 In case, Licensee draws power more than the connected load, his electricity connection shall be disconnected. The electricity connection shall be provided back on first occasion only when Licensee pays necessary penalty as per State ERC norms and removes excess load. On the subsequent occasion, DMRC reserves the right to revoke the license and forfeit the interest free security deposit after adjustment of all dues what so ever.
13.15 In case, the Licensee is found misusing Electricity or tampering with the Energy meter, suitable action shall be taken to respective State Electricity Act.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables Licensee shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‘s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantBidder. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Bidder or at a common meter room/board. Applicant Bidder shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safetysafety (if installed within his premises).
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricityBidder.
13.3 That the use Only FRLS/FRLSZH (as applicable) cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Licensee premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will Licensee shall also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant Licensee shall use FRZHLS copper FRLS/FRLSZH copper/aluminum wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s DMRC‘s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant 14.1 Licensee will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 14.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicantapplicant in line with scope of work provided by DMRC. Approval to the layouts/ schemes/ layouts/schemes/details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use 14.3 Only FRLS /FRLSZH cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to licensee premises in the underground stationsrigid GI Conduit pipe in line with specifications of Electrical works provided to applicant by DMRC.
13.4 Applicant 14.4 Licensee will also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/ caping. The Applicant Licensee shall use FRZHLS FRLS /FRLSZH copper wire of the required size in line with specifications of Electrical works provided to applicant by DMRC (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 14.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW, 10kVA/5 KVA in line with specifications of Electrical works provided to applicant by DMRC. Electrical load requirement exceeding 10 KW above will be given on 3-3- phase, 415V, 50Hz subject to availability.
13.6 Applicant 14.6 Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‟s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant will also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s DMRC‟s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max connected load up to 10 KW, Electrical load requirement exceeding 10 KW will be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s DMRC‟s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops shop/bare spaces only XLPE insulated armored copper conductor FRLS/ LSZH (as applicable) cables shall be used. Applicant will Licensee shall have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‘s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantBidder. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Bidder or at a common meter room/boardboard (Common meter room is locked & key, access is not permitted to licensee). Applicant Bidder shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicantBidder. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant Licensee hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant will Licensee shall also do wiring within his shop/bare space/stall/KIOSK by using GI conduit. The Applicant Licensee shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s DMRC‘s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will Licensee shall have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant Licensee shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s DMRC‘s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant Bidder shall be submitted by the ApplicantLicensee.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant will also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max connected load up to 10 KW, Electrical load requirement exceeding 10 KW will be given on 3-3- phase, 415V, 50Hz subject to availability.
13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‟s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant will also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s DMRC‟s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max connected load up to 10 KW, Electrical load requirement exceeding 10 KW will be given on 3-3- phase, 415V, 50Hz subject to availability.
13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s DMRC‟s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant Licensee will have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‟s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use Only FRLS cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to licensee premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant Licensee will also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant Licensee shall use FRZHLS FRLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s DMRC‟s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant Licensee will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant Licensee will have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant Licensee shall use Energy efficient lighting lighting& shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than that 100 Lux in any case.
13.10 Applicant Licensee shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Licensee‟s cost shall carry the entire work. DMRC‟s representative may inspect and supervise the work.
13.11 Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s DMRC‟s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the ApplicantLicensee. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Licensee will not be allowed to provide Room Heating appliance of any kind.
Appears in 1 contract
Samples: Licensing Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant Licensee will have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‟s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant licensee hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant Licensee will also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant Licensee shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s DMRC‟s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW, Electrical load requirement exceeding 10 KW will be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant Licensee will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant Licensee will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant Licensee shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s DMRC‟s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the ApplicantLicensee.
Appears in 1 contract
Samples: Licensing Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables Licensee shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s ELCB‘s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantBidder. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Bidder or at a common meter room/board. Applicant Bidder shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safetysafety (if installed within his premises).
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricityBidder.
13.3 That the use Only FRLS/FRLSZH (as applicable) cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Licensee premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will Licensee shall also do wiring within his shop/stallbare space/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant Licensee shall use FRZHLS copper FRLS/FRLSZH copper/aluminum wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s DMRC‘s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor FRLS/ LSZH (as applicable) cables shall be used. Applicant will Licensee shall have to provide a Low voltage switch-switch- board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicantApplicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant Applicant or at a common meter room/boardboard (Common meter room is locked & key, access is not permitted to licensee). Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicantApplicant. Approval to the layouts/ schemes/ details shall be taken from DMRC O&M wing. The Applicant Licensee hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use of any PVC material is not permitted in the underground stations.
13.4 Applicant will Licensee shall also do wiring within his shop/stall/KIOSK by using GI conduit. The Applicant Licensee shall use FRZHLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, fan etc. shall be as per DMRC’s approval).
13.5 DMRC will shall provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW, Electrical load requirement exceeding 10 KW will shall be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant Licensee shall be given only normal power supply available in station premises. Applicant Licensee may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant Licensee shall not be permitted to use any standby Diesel Generator Sets. Applicant will Licensee shall only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will shall also be taken as a part of total connected load.
13.8 The Total Demand Load & Total Connected load shall be treated as same. Applicant will Licensee shall have to pay applicable demand charges as per the Total Connected load only.
13.9 Applicant Licensee shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant Licensee shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant Licensee shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant Applicant shall be submitted by the ApplicantLicensee.
Appears in 1 contract
Samples: License Agreement
Others. 13.1 From the DMRC DB to main MCB / MCB of shops only XLPE insulated armored copper conductor LSZH cables shall be used. Applicant will have to provide a Low voltage switch-board with MCBs& ELCB’s of required capacity with Electronics Static Energy Meters having provision of MDI, XXX etc. of required capacity at his cost conforming to relevant BIS standards and of approved make along with test certificate shall be arranged by the applicant. The meter shall be installed and sealed by DMRC, either within the premises of the applicant or at a common meter room/board. Applicant shall not tamper with or disturb the meter in any manner whatsoever, and shall be responsible for its safety.
13.2 DMRC shall provide supply, if available, at one fixed point as per DMRC plan. All cabling work to tap off the supply from the fixed point and to avail it within his premises shall be done by the applicant. Approval to the layouts/ schemes/ layouts/schemes/details shall be taken from DMRC O&M wing. The Applicant hereby voluntarily and unequivocally agrees not to seek any claim, damage, compensating or any other consideration what so ever on account of time and cost associated in making provision of electricity.
13.3 That the use Only FRLS cable of any PVC material is not permitted required size shall be used for tapping off supply from DMRC fixed supply to Applicant premises in the underground stationsrigid GI Conduit pipe.
13.4 Applicant will also do wiring within his shop/stall/KIOSK stall by using GI conduitconduit or fire resistance PVC casing/caping. The Applicant shall use FRZHLS FRLS copper wire of the required size (the wiring scheme, the type of wiring, size of wires, various loads, plug point, light, light fan etc. shall be as per DMRC’s approval).
13.5 DMRC will provide Power Supply of single phase, 230V, 50Hz for a max max. connected load up to 10 KW10kW, Electrical load requirement exceeding 10 KW will be given on 3-phase, 415V, 50Hz subject to availability.
13.6 Applicant shall be given only normal power supply available in station premises. Applicant may use suitable voltage stabilizers and power factor correction equipment as per his requirement. DMRC shall not be providing any standby power supply from station DG set or UPS.
13.7 Applicant shall not be permitted to use any standby Diesel Generator Sets. Applicant will only be the permitted to use standby UPS/Inverter System with maintenance free battery. The Load of such standby UPS/Inverter system will also be taken as a part of total connected load.
13.8 The Total Demand Load Load& Total Connected load shall be treated as same. Applicant will have to pay applicable demand charges as per the Total Connected load onlyLoad Only.
13.9 Applicant shall use Energy efficient lighting & shall provide proper Lighting fixtures, Lamps, Electronic Ballast etc. Applicant shall provide uniform & good illumination level not less than 100 Lux in any case.
13.10 Applicant shall use reputed Brand/make Electrical wiring and switch gear items. The Electrical Contractor/agency at Applicant’s cost shall carry the entire work. DMRC’s representative may inspect and supervise the work.
13.11 Applicant shall provide proper Earthing connection as per the applicable standards and shall terminate the same to the DMRC’s Distribution Board or to any other place as directed by the DMRC. Installation Test Report issued by licensed electrical wiring contractor in the prescribed format (available with the application form) and countersigned by the applicant shall be submitted by the Applicant. Every shop/ property Development area must have enough Fire Extinguishers as stipulated.
13.12 Applicant will not be allowed to provide Room Heating appliance of any kind.
13.13 The power shall be supplied normally at the rate of 0.5 KVA/Xx.Xxx. of space licensed out. Minimum load to be given shall be 2 KVA on which the demand charges as applicable shall be paid by the Applicant. Additional power up to 10 kW on single phase and thereafter on three phase system if required by the Applicant will be supplied subject to availability at an additional cost and conditions to be stipulated by DMRC.
13.14 In case, Applicant draws power more than the connected load, his electricity connection shall be disconnected. The electricity connection will be provided back on first occasion only when Applicant pays necessary penalty as per State ERC norms and removes excess load. On the subsequent occasion, DMRC reserves the right to revoke the license and forfeit the interest free security deposit.
13.15 In case, the Applicant is found misusing Electricity or tampering with the Energy meter, a token penalty of Rs. 1000/- will be charged from him along with disconnection of power supply. Reconnection of power supply will be done only after charging Rs. 100/- as reconnection fee and clearance of all dues duly obtaining approval of Competent Authority of DMRC.