Common use of Power Factor Design Criteria Clause in Contracts

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals of the Electric Generating Unit at a power factor within the range of 0.95 leading to 0.90 lagging, unless the CAISO has established different requirements that apply to all generators in the Balancing Authority Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H of this LGIA.

Appears in 48 contracts

Samples: Large Generator Interconnection Agreement, Caiso Tariff Appendix Z, Caiso Tariff Appendix Hh

AutoNDA by SimpleDocs

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIAparagraph shall not apply to wind generators.

Appears in 15 contracts

Samples: Surplus Large Generator Interconnection Agreement, Surplus Large Generator Interconnection Agreement, Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Distribution Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for The requirements of this paragraph shall not apply to wind generators are provided in generators; rather, the requirements of Appendix H of this LGIAshall apply to wind generators.

Appears in 15 contracts

Samples: Generator Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Distribution Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIAparagraph shall not apply to wind generators; rather, the requirements of Appendix G shall apply to wind generators.

Appears in 5 contracts

Samples: Service Agreement, Standard Large Generator Interconnection Agreement, California Edison Company

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals of the Electric Generating Unit at a power factor within the range of 0.95 leading to 0.90 lagging, unless the CAISO ISO has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix Part H of this LGIA.

Appears in 4 contracts

Samples: Large Generator Interconnection Agreement, Large Generator Interconnection Agreement, Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the minimum range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIAparagraph shall not apply to wind generators.

Appears in 3 contracts

Samples: www.transmissionhub.com, www.transmissionhub.com, www.transmissionhub.com

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO System Operator or Interconnecting Transmission Owner has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basisbasis and in accordance with ISO New England Operating Documents, Applicable Reliability Standards, or successor documents. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIAparagraph shall not apply to wind generators.

Appears in 2 contracts

Samples: Large Generator, Standard Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Distribution Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIAparagraph shall not apply to wind generators; rather, the requirements of Appendix G shall apply to wind generators.

Appears in 2 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIAparagraph shall not apply to wind generators. Non-synchronous generators shall only be required to maintain the above power factor when their output is above 10 percent of the Generating Facility Capacity.

Appears in 2 contracts

Samples: www.ferc.gov, omb.report

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery for the Large Generating Facility at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO System Operator or Interconnecting Transmission Owner has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided basis and in Appendix H of this LGIAaccordance with ISO New England Operating Documents, Applicable Reliability Standards, or successor documents.

Appears in 2 contracts

Samples: Large Generator Interconnection Agreement, Large Generator Interconnection Agreement

Power Factor Design Criteria. The For all Generating Facilities other than Asynchronous Generating Facilities, the Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals of the Electric Generating Unit at a power factor within the range of 0.95 leading to 0.90 lagging, unless the CAISO has established different requirements that apply to all generators in the Balancing Authority Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H of this LGIA.comparable

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria See Appendix G for wind generators are provided in Appendix H of this LGIAadditional details.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all synchronous generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H of this LGIA.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals of the Electric Generating Unit at a power factor within the range of 0.95 leading to 0.90 lagging, unless the CAISO ISO has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H of this LGIA.

Appears in 1 contract

Samples: www.caiso.com

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for The requirements of this paragraph shall not apply to wind generators are provided in Appendix H of this LGIAunless mutually agreed to by the Parties.

Appears in 1 contract

Samples: Study Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Qualifying Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Company has established different requirements that apply to all synchronous generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIA.paragraph shall not apply to wind generators.‌

Appears in 1 contract

Samples: Agreement

AutoNDA by SimpleDocs

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H of this LGIA.

Appears in 1 contract

Samples: Study Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for The requirements of Appendix G to this LGIA shall apply to wind generators are provided in Appendix H of this LGIAgenerators.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Distribution Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIAparagraph shall not apply to wind generators; rather, the requirements of Appendix HH shall apply to wind generators.

Appears in 1 contract

Samples: Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO JPP has established different requirements that apply to all interconnected generators in the Balancing Authority Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H The requirements of this LGIAparagraph shall not apply to wind generators.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Area on a comparable basis. Power A non-synchronous generator shall maintain a power factor design criteria for wind generators are provided with the range of 0.95 leading to 0.95 lagging, measured at the high side of the GSU as defined in Appendix H of this LGIAGIA.

Appears in 1 contract

Samples: Study Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider or Transmission Operator has established different requirements that apply to all generators in the Balancing Authority Area on a comparable basis. Power factor design criteria for The requirements of this paragraph shall not apply to wind generators are provided unless the need for such criteria has been established in Appendix H of this LGIAthe System Impact Study.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of of‌ 0.95 leading to 0.90 0.95 lagging, unless the CAISO Distribution Provider has established different requirements that apply to all generators in the Balancing Authority Control Area on a comparable basis. Power factor design criteria for The requirements of this paragraph shall not apply to wind generators are provided in generators; rather, the requirements of Appendix H of this LGIAshall apply to wind generators.

Appears in 1 contract

Samples: Clustering Large Generator Interconnection

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals of the Electric Generating Unit at a power factor within the range of 0.95 leading to 0.90 lagging, unless the CAISO has established different requirements that apply to all generators in the Balancing Authority Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H of this LGIA.comparable

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the minimum range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Transmission Provider has established different requirements that apply to all generators in the Balancing Authority Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H Unless otherwise required by Applicable Laws and Regulations or Applicable Reliability Standards, the requirements of this LGIAparagraph shall not apply to wind generators.

Appears in 1 contract

Samples: Cluster Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at a power factor at the terminals Point of the Electric Generating Unit Interconnection at a power factor within the range of 0.95 leading to 0.90 0.95 lagging, unless the CAISO Operating Agent has established different requirements that apply to all interconnected generators in the Balancing Authority Area on a comparable basis. Power factor design criteria for wind generators are provided in Appendix H of this LGIA.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement