Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of
Appears in 15 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Power Factor Design Criteria. Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of
Appears in 10 contracts
Samples: Qualifying Facility Large Generator Interconnection Agreement, Qualifying Facility Large Generator Interconnection Agreement, Clustering Large Generator Interconnection Agreement (Clgia)
Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range ofrated
Appears in 7 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement
Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the minimum range ofof 0.95 leading to 0.95 lagging, unless Transmission Provider has established different requirements that apply to all generators in the Balancing Authority on a comparable basis
Appears in 2 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement
Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery for the Large Generating Facility at continuous rated power output at the Point of Interconnection at a power factor within the range of
Appears in 2 contracts
Samples: Service Agreements, Service Agreement
Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within factors over 0.95 leading to 0.95 lagging, unless Transmission Provider has established different requirements that apply to all generators in the range ofLocal
Appears in 2 contracts
Samples: Generator Interconnection Agreement, Power Purchase Agreement
Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within factors over 0.95 leading to 0.95 lagging, unless Transmission Provider has established different requirements that apply to all generators in the range ofLocal Balancing
Appears in 2 contracts
Samples: Generator Interconnection Agreement, Generator Interconnection Agreement
Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within the range offactors over 0.95 leading to 0.95 lagging, unless Transmission Provider has established
Appears in 1 contract
Samples: Generator Interconnection Agreement
Power Factor Design Criteria. Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range ofof 0.95 leading to
Appears in 1 contract
Samples: Standard Large Generator Interconnection Agreement (Lgia)
Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point terminals of Interconnection at a power factor within the range ofElectric
Appears in 1 contract
Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at a power factor at the Point of Interconnection at a power factor within the range ofof 0.95 leading to 0.95 lagging, unless Operating Agent has established different requirements that apply to all interconnected generators on a comparable basis.
Appears in 1 contract
Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range ofdelivery
Appears in 1 contract
Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point terminals of Interconnection the Electric Generating Unit at a power factor within the range ofof 0.95 leading to
Appears in 1 contract