Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of

Appears in 15 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

AutoNDA by SimpleDocs

Power Factor Design Criteria. Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range of

Appears in 10 contracts

Samples: Qualifying Facility Large Generator Interconnection Agreement, Qualifying Facility Large Generator Interconnection Agreement, Clustering Large Generator Interconnection Agreement (Clgia)

Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range ofrated

Appears in 7 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the minimum range ofof 0.95 leading to 0.95 lagging, unless Transmission Provider has established different requirements that apply to all generators in the Balancing Authority on a comparable basis

Appears in 2 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement

Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery for the Large Generating Facility at continuous rated power output at the Point of Interconnection at a power factor within the range of

Appears in 2 contracts

Samples: Service Agreements, Service Agreement

Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within factors over 0.95 leading to 0.95 lagging, unless Transmission Provider has established different requirements that apply to all generators in the range ofLocal

Appears in 2 contracts

Samples: Generator Interconnection Agreement, Power Purchase Agreement

Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within factors over 0.95 leading to 0.95 lagging, unless Transmission Provider has established different requirements that apply to all generators in the range ofLocal Balancing

Appears in 2 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement

Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a all power factor within the range offactors over 0.95 leading to 0.95 lagging, unless Transmission Provider has established

Appears in 1 contract

Samples: Generator Interconnection Agreement

AutoNDA by SimpleDocs

Power Factor Design Criteria. Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range ofof 0.95 leading to

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement (Lgia)

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point terminals of Interconnection at a power factor within the range ofElectric

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain a composite power delivery at continuous rated power output at a power factor at the Point of Interconnection at a power factor within the range ofof 0.95 leading to 0.95 lagging, unless Operating Agent has established different requirements that apply to all interconnected generators on a comparable basis.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Power Factor Design Criteria. Interconnection Customer shall design the Generating Facility to maintain be capable of maintaining a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range ofdelivery

Appears in 1 contract

Samples: Provisional Generator Interconnection Agreement

Power Factor Design Criteria. The Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the Point terminals of Interconnection the Electric Generating Unit at a power factor within the range ofof 0.95 leading to

Appears in 1 contract

Samples: Standard Large Generator Interconnection Agreement