Severe Disturbances. Operation of the Merchant Transmission Facility may be temporarily suspended for disturbances more severe than defined in Minor AC Voltage Disturbances above. Unless the voltage disturbance at either terminal of the Merchant Transmission Facility exceeds the extreme disturbance criteria listed in Criteria for Permanent Blocking and Tripping below, the Merchant Transmission Facility shall commence recovery within one cycle of the recovery of the PJM and New York State Transmission System voltage to a value greater than 0.8pu in all phases.