Testing of the Metering Equipment. 7.2.1. The Main and Check Meters shall be tested for accuracy, with a portable standard meter, by the National accredited Labs and sealed by the MSEDCL at its own cost. Purchaser shall carry out the calibration, periodical testing, sealing and maintenance of meters in the presence of the authorized representative(s) of the seller and the representative of the Seller shall sign on the results thereof. 7.2.2. The frequency of meter testing shall be annual. All the meters will be tested only at the Metering Point. Purchaser will provide a copy of the test reports to Seller. 7.2.3. If during testing, both the Main and Check Meter are found within the permissible limit of error i.e.0.2%, the energy computation will be as per the Main Meter. If during test, any of the Main Meters is found to be within the permissible limits of error but the corresponding Check Meter is beyond the permissible limit; the energy computation will be as per the Main Meter. The Check Meter shall be calibrated immediately. 7.2.4. If during the tests, any of the Main Meters is found to be beyond permissible limits of error, but the corresponding Check Meters is found to be within the permissible limits of error, then the energy computation for the month upto date and time of such test check shall be in accordance with Check Meter. The Main Meter shall be calibrated immediately and the energy for the period thereafter shall be as per the calibrated Main Meter. 7.2.5. If during any of the monthly meter readings, the variation between the Main meter and the Check meter is more than 0.5 %, all the meters shall be re-tested and calibrated at the Seller’s cost immediately by Purchaser. During this period energy recorded with SCADA shall be used for billing & payment purposes. 7.2.6. For all times the reading of the Main meter only will be considered except in rarest conditions such as maintenance, repairs, testing or discrepancy in meter reading with compare to check meters then the Check meter reading may be considered
Appears in 3 contracts
Samples: Power Purchase Agreement, Power Purchase Agreement, Power Purchase Agreement
Testing of the Metering Equipment. 7.2.1. 7.3.1 The Main and Check Meters shall be tested for accuracy, with a portable standard meter, by the National accredited Labs and sealed by the MSEDCL at its own cost. Purchaser shall carry out the calibration, periodical testing, sealing and maintenance of meters in the presence of the authorized representative(s) of the seller and the representative of the Seller shall sign on the results thereof.
7.2.2. 7.3.2 The frequency of meter testing shall be annual. All the meters will be tested only at the Metering Point. Purchaser will provide a copy of the test reports to Seller.
7.2.3. 7.3.3 If during testing, both the Main and Check Meter are found within the permissible limit of error i.e.0.2i.e. 0.2%, the energy computation will be as per the Main Meter. If during test, any of the Main Meters is found to be within the permissible limits of error but the corresponding Check Meter is beyond the permissible limit; the energy computation will be as per the Main Meter. The Check Meter shall be calibrated immediately.
7.2.4. 7.3.4 If during the tests, any of the Main Meters is found to be beyond permissible limits of error, but the corresponding Check Meters is found to be within the permissible limits of error, then the energy computation for the month upto date and time of such test check shall be in accordance with Check Meter. The Main Meter shall be calibrated immediately and the energy for the period thereafter shall be as per the calibrated Main Meter.
7.2.5. 7.3.5 If during any of the monthly meter readings, the variation between the Main meter and the Check meter is more than 0.5 0.5%, all the meters shall be re-tested and calibrated at the Seller’s cost immediately by Purchaser. During this period energy recorded with SCADA shall be used for billing & payment purposes.
7.2.6. 7.3.6 For all times the reading of the Main meter only will be considered except in rarest conditions such as maintenance, repairs, testing or discrepancy in meter reading with compare to check meters then the Check meter reading may be considered
Appears in 1 contract
Samples: Power Purchase Agreement
Testing of the Metering Equipment. 7.2.1. 7.2.1 The Main and Check Meters shall be tested for accuracy, with a portable standard meter, by the National accredited Labs and sealed by the MSEDCL at its own cost. Purchaser MSEDCL/MSETCL/STU shall carry out the calibration, periodical testing, sealing and maintenance of meters in the presence of the authorized representative(s) of the seller FSPD and the representative of the Seller FSPD shall sign on the results thereof.
7.2.2. 7.2.2 The frequency of meter testing shall be annual. All the meters will be tested only at the Metering Point. Purchaser will provide a copy of the test reports to Seller.
7.2.3. 7.2.3 If during testing, both the Main and Check Meter are found within the permissible limit of error i.e.0.2i.e. 0.2%, the energy computation will be as per the Main Meter. If during test, any of the Main Meters is found to be within the permissible limits of error but the corresponding Check Meter is beyond the permissible limit; the energy computation will be as per the Main Meter. The Check Meter shall be calibrated immediately.
7.2.4. 7.2.4 If during the tests, any of the Main Meters is found to be beyond permissible limits of error, but the corresponding Check Meters is found to be within the permissible limits of error, then the energy computation for the month upto date and time of such test check shall be in accordance with Check Meter. The Main Meter shall be calibrated immediately and the energy for the period thereafter shall be as per the calibrated Main Meter.
7.2.5. 7.2.5 If during any of the monthly meter readings, the variation between the Main meter and the Check meter is more than 0.5 0.5%, all the meters shall be re-tested and calibrated at the Seller’s cost immediately by Purchaser. During this period energy recorded with SCADA shall be used for billing & payment purposes.
7.2.6. 7.2.6 For all times the reading of the Main meter only will be considered except in rarest conditions such as maintenance, repairs, testing or discrepancy in meter reading with compare to check meters then the Check meter reading may be considered
Appears in 1 contract
Samples: Power Purchase Agreement