Transformer Protection. With the 115kV bus becoming a breakered transmission bus, the existing 64/TR1 relay will need to be rewired and reset to allow the TR1 terminal to have the functionality required. The relay will be connected to one of the CT cores in the new column CT to provide breaker failure functionality for the transformer TR1 circuit switcher CS6177. Upon failure of CS6177, this relay will operate the 115kV bus breaker failure lockout relay. The relay will also provide reclosing functionality for CS6177 to support the 115kV automatic bus restoration scheme, and it will also serve to provide an additional overcurrent scheme for protection of TR1.

Appears in 4 contracts

Samples: Service Agreement, Service Agreement, Transmission Project Interconnection Agreement

AutoNDA by SimpleDocs

Transformer Protection. With the 115kV bus becoming a breakered transmission bus, the existing 64/TR1 a single multifunction relay will need to be rewired and reset added to allow the TR1 terminal to have the functionality required. The relay will be connected to one the middle CT core on the high side bushings of the CT cores in the new column CT existing transformer TR1 to provide breaker failure functionality for the transformer TR1 circuit switcher CS6177CS6199. Upon failure of CS6177CS6199, this relay will operate the 115kV 115 kV bus breaker failure lockout relay. The relay will also provide reclosing functionality for CS6177 CS6199 to support the 115kV 115 kV automatic bus restoration scheme, and it will also serve to provide an additional overcurrent scheme for protection of TR1.. The existing electromechanical TR1 overcurrent scheme will be removed, but the existing TR1 differential will remain. A-12 SERVICE AGREEMENT NO. 2599

Appears in 2 contracts

Samples: Service Agreement, Service Agreement

AutoNDA by SimpleDocs

Transformer Protection. With the 115kV bus becoming a breakered transmission bus, the existing 64/TR1 a single multifunction relay will need to be rewired and reset added to allow the TR1 terminal to have the functionality required. The relay will be connected to one the middle CT core on the high side bushings of the CT cores in the new column CT existing transformer TR1 to provide breaker failure functionality for the transformer TR1 circuit switcher CS6177CS6199. Upon failure of CS6177CS6199, this relay will operate the 115kV 115 kV bus breaker failure lockout relay. The relay will also provide reclosing functionality for CS6177 CS6199 to support the 115kV 115 kV automatic bus restoration scheme, and it will also serve to provide an additional overcurrent scheme for protection of TR1. The existing electromechanical TR1 overcurrent scheme will be removed, but the existing TR1 differential will remain.

Appears in 1 contract

Samples: Transmission Project Interconnection Agreement