Warning Tape Sample Clauses

Warning Tape. 1. Water mains shall be installed with polyethylene film warning tape manufactured for marking and identifying underground water utilities. Tape shall be a minimum of 2 inches (50 mm) wide and 4 mils thick, blue in color, with continuously printed letters reading “CAUTION BURIED WATER LINE BELOW”.
AutoNDA by SimpleDocs
Warning Tape. 1. Inert polyethylene, non metallic, impervious to known alkalis, acids, chemical reagents, and solvents likely to be encountered in soil. 2. Thickness: 5 mils minimum. 3. Width: 4 inches minimum. 4. Identifying Lettering: Minimum 1-inch high, permanent black lettering imprinted continuously over entire length.
Warning Tape. Sanitary sewer mains shall be installed with polyethylene film warning tape manufactured for marking and identifying underground wastewater utilities. Tape shall be a minimum of 2 inches (50 mm) wide and 4 mils thick, green in color, with continuously printed letters reading “CAUTION BURIED SEWER LINE BELOW”.
Warning Tape. All electric services for the small cell wireless infrastructure must be marked with warning tape. Detectable electrical warning tape must consist of pre‐manufactured non‐ adhesive polyethylene material that is unaffected by acids, alkalines, and other soil components. The tape must be red in color and must be, at a minimum, 3.5 mils thick and 6 inches wide. Its tensile strength must be 2,500 psi lengthwise. The electrical tape must include the following identification printed in black letters continuously along the length of the tape: “CAUTION BURIED ELECTRIC LINE BELOW”. The identification note and color of tape must conform to the requirements of the “American Public Works Association (APWA) Uniform Color Codes (Red) – Electrical Power Lines, Cables, Conduit and Lighting Cables.”
Warning Tape. A. Standard, 4-Mil polyethylene 3 inches wide tape non-detectable type, red with black letters, and imprinted with “CAUTION BURIED ELECTRONIC SAFETY AND SECURITY CABLE BELOW”.
Warning Tape. 1 A 152mm wide yellow warning marker tape will be placed in the trench on centerline of each duct bank approximately 300mm below final grade.
Warning Tape. As a protective measured for buried lines crossing Company’s Easement Tract, vinyl direct buried warning tape (or mesh where required), XxXxxxxx- Xxxx No. 8288T12 or equal, shall be placed at least 15 inches above the crossing line for the entire width of the Company pipeline Easement Tract.
AutoNDA by SimpleDocs
Warning Tape. A suitable yellow PVC tape 0.5 mm thick and 100 mm wide shall be placed 30 cm above the installed optical fiber cable for indication to the excavators of the presence of optical fiber cable with some warning note.
Warning Tape. The tape should be installed at approximately 1/3 to 1/2 of the depth of cover over all conduits except when bored. All warning tape shall be polyethylene plastic tape, a minimum width of 3” in agreement with Uniform Color Code and imprinted with the words “Caution-Buried Fiber Optic Cable Below” at no more than 48-inches intervals. Minimum thickness of the tape shall be 0.004 inches. Tape shall have a minimum strength of 1750 PSI lengthwise and 1500 PSI. Tape shall be manufactured with integral wires, foil backing, or other means of enabling detection by a metal detector or underground cable detector typically used in the OSP industry when tape is buried up to 3-feet deep. The materials in the warning tape shall be chemically inert and shall not degrade when exposed to acids, alkalis, and other destructive substances found in soil.
Warning Tape. 12-inches long; of each color
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!