Autotransformer Protection. These shall have the following protections:
Autotransformer Protection. These shall have the following protections:
i) Numerical Differential Protection
ii) Numerical Restricted Earth Fault Protection
iii) Numerical Back-up Over-Current and Earth Fault Protection on High Voltage (HV) and Intermediate Voltage (IV) side
iv) Numerical Over Fluxing Protection on HV and IV side
v) Numerical Overload Alarm Further, Numerical Back-up Over-current and earth fault protection on HV and IV side of autotransformer shall not be combined with other protective functions in the main relays and shall be independent relays. Besides these, power transformers shall also be provided with Xxxxxxxx relay, Magnetic Oil Gauge (MOG) with low oil level alarm, protection against high oil and winding temperature and pressure relief device etc. Suitable monitoring, control (operation of associated circuit breaker and isolator) and protection for LT auxiliary transformer connected to tertiary winding of auto-transformer for the purpose of auxiliary supply shall be provided. The over current and other necessary protection shall be provided for the auxiliary transformer. These protection and control may be provided as built- in feature either in the bay controller to be provided for the auxiliary system or in the control and protection IEDs to be provided for autotransformer.