We use cookies on our site to analyze traffic, enhance your experience, and provide you with tailored content.

For more information visit our privacy policy.

Common use of Breaker Clause in Contracts

Breaker. Breaker failure protection shall be provided for the 115kV breaker; this protection must trip the appropriate adjacent breakers and send DTT to the Connecting Transmission Owner’s Arcade and Five Mile Substations. For loss of SF6, the breaker must trip and block close. DTT received from Connecting Transmission Owner’s Arcade and Five Mile Substations will be required to trip the Interconnection Customer's 115kV breaker for a line relay operation or breaker failure at Connecting Transmission Owner’s Arcade and Five Mile Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.

Appears in 10 contracts

Samples: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Interconnection Agreement

AutoNDA by SimpleDocs
Draft better contracts in just 5 minutes Get the weekly Law Insider newsletter packed with expert videos, webinars, ebooks, and more!