Common use of Breaker Clause in Contracts

Breaker. Breaker failure protection shall be provided for the 115kV breaker; this protection must trip the appropriate adjacent breakers and send DTT to the Connecting Transmission Owner’s Arcade and Five Mile Substations. For loss of SF6, the breaker must trip and block close. DTT received from Connecting Transmission Owner’s Arcade and Five Mile Substations will be required to trip the Interconnection Customer's 115kV breaker for a line relay operation or breaker failure at Connecting Transmission Owner’s Arcade and Five Mile Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.

Appears in 8 contracts

Samples: Service Agreement, Service Agreement, Service Agreement

AutoNDA by SimpleDocs

Breaker. Breaker failure protection shall be provided for the 115kV breaker; this protection must 115 kV circuit breaker that will trip the appropriate adjacent breakers and send DTT direct transfer trip (“DTT”) to the Connecting Transmission Owner’s Arcade Xxxxxx and Five Mile Cortland Substations. For loss of SF6, the breaker must will trip and block close. A DTT received receive from Connecting Transmission Owner’s Arcade the Xxxxxx and Five Mile Cortland Substations will be required to trip the Interconnection Customer's 115kV ’s R180 breaker for a line relay operation or breaker failure at Connecting Transmission Owner’s Arcade the Xxxxxx and Five Mile Cortland Substations. The Interconnection Customer shall provide on/off switches DTT transmit and receive schemes will use additional channels available on the GARD 8000 for the DTT schemesline protection.

Appears in 3 contracts

Samples: Service Agreement, Service Agreement, Service Agreement

AutoNDA by SimpleDocs
Time is Money Join Law Insider Premium to draft better contracts faster.