Breaker. Breaker failure protection shall be provided for the 115kV breaker. This protection must trip the appropriate adjacent breakers and send direct transfer trip to the Eastover and Schaghticoke Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Interconnection Customer’s interrupter fails to interrupt for internal station faults and loss of SERVICE AGREEMENT NO. 2638 SF6 condition, Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Schaghticoke and Eastover Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Schaghticoke and Eastover Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 4 contracts
Samples: Service Agreement, Service Agreement, Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker. This breaker R5; this protection must trip the appropriate adjacent breakers Interconnection Customer’s 115kV breaker and send direct transfer trip DTT to the Eastover North Xxxx and Schaghticoke Hoosick Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Interconnection Customerfacility’s interrupter fails to interrupt for internal station faults and loss of SF6 condition, the SERVICE AGREEMENT NO. 2638 SF6 condition, 2756 Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Schaghticoke North Xxxx and Eastover Hoosick Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, operation or breaker failure at the Schaghticoke North Xxxx and Eastover SubstationsHoosick substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 3 contracts
Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker. This ; this protection must trip the appropriate adjacent breakers Interconnection Customer’s 115kV breaker and send direct transfer trip DTT to the Eastover Mohican and Schaghticoke Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Interconnection CustomerSmall Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SERVICE AGREEMENT NO. 2638 SF6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Mohican and Schaghticoke and Eastover Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Mohican or Schaghticoke and Eastover Substations. The Interconnection Customer shall provide onON/off OFF switches for the DTT schemes.
Appears in 2 contracts
Samples: Standard Small Generator Interconnection Agreement, Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker. This breaker R5; this protection must trip the appropriate adjacent breakers Interconnection Customer’s 115kV breaker and send direct transfer trip DTT to the Eastover North Xxxx and Schaghticoke Hoosick Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Interconnection Customerfacility’s interrupter fails to interrupt for internal station faults and loss of SERVICE AGREEMENT NO. 2638 SF6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Schaghticoke North Xxxx and Eastover Hoosick Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, operation or breaker failure at the Schaghticoke North Xxxx and Eastover SubstationsHoosick substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract
Samples: Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV 46 kV breaker. This protection must trip the appropriate adjacent breakers Interconnection Customer’s 46 kV breaker and send direct transfer trip DTT to the Eastover Connecting Transmission Owner’s Inghams and Schaghticoke Valley Substations. For loss of SF6SF-6, the breaker must trip and block close. (Note: When the Interconnection CustomerSmall Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SERVICE AGREEMENT NO. 2638 SF6 SF-6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV 46 kV system for remote backup.) DTT receive from the Schaghticoke Inghams and Eastover Valley Substations will be required to trip the Interconnection Customer’s 115kV 46 kV circuit breaker for a line relay operation, operation or breaker failure at the Schaghticoke Inghams and Eastover Valley Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract
Samples: Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker. This protection must trip the appropriate adjacent breakers and send direct transfer trip to the Eastover and Schaghticoke SubstationsConnecting Transmission Owner’s Ticonderoga Substation. For loss of SF6, the breaker must trip and block close. (Note: When the Interconnection CustomerSmall Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SERVICE AGREEMENT NO. 2638 2666 loss of SF6 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Schaghticoke and Eastover Substations Ticonderoga Substation will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Schaghticoke and Eastover Substations(R2). The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract
Samples: Service Agreement
Breaker. Breaker failure protection shall be provided for the 115kV breaker. This protection must trip the appropriate adjacent breakers and send direct transfer trip to the Eastover Mohican and Schaghticoke Battenkill Substations. For loss of SF6, the breaker must trip and block close. (Note: When the Interconnection CustomerSmall Generating Facility’s interrupter fails to interrupt for internal station faults and loss of SF SERVICE AGREEMENT NO. 2638 SF6 2720 condition, the Interconnection Customer is not to rely on the Connecting Transmission Owner’s 115kV system for remote backup.) DTT receive from the Schaghticoke Battenkill and Eastover Mohican Substations will be required to trip the Interconnection Customer’s 115kV breaker for a line relay operation, or breaker failure at the Schaghticoke Battenkill and Eastover Mohican Substations. The Interconnection Customer shall provide on/off switches for the DTT schemes.
Appears in 1 contract