Circuit Breakers. The circuit breakers to be used shall be of live tank type and be provided with seismic dampers, if necessary. The circuit breakers shall have the following supplementary characteristics: Short-circuit duration Total opening time Sequence of operation: a) Operation of reactors CO-15”-CO b) Operation of lines O-0.3”-CO-3’-CO Type Outdoor
Appears in 2 contracts
Samples: Concession Contract, Concession Contract
Circuit Breakers. The circuit breakers to be used shall be of live or dead tank type and be provided with seismic dampers, if necessary. The circuit breakers shall have the following supplementary characteristics: Short-circuit duration 1” 1” Total opening time 3 cycles 3 cycles Sequence of operation:
: a) Operation of reactors CO-15”-CO
the transformer b) Operation of lines CO-15”-CO O-0.3”-CO-3’-CO CO-15”-CO O-0.3”-CO-3’-CO Type Outdoor Outdoor
Appears in 2 contracts
Samples: Concession Contract, Concession Contract