Current levels. All switchgear (circuit breakers and disconnectors) shall meet the following characteristics: 220kV Minimum rated current 2500 A Three-phase short-circuit breaking capacity, 1s 40 kA Three-phase short-circuit breaking capacity 104kApeak The reactor circuit breakers shall comply with Standard IEEE Std.C37.015 regarding current opening and closing requirements.

Appears in 3 contracts

Samples: SGT Concession Contract, SGT Concession Contract, SGT Concession Contract

AutoNDA by SimpleDocs

Current levels. All switchgear (circuit breakers and disconnectors) shall meet the following characteristics: 220kV Minimum rated current 2500 A ThreeXxxxx-phase shortxxxxx xxxxx-circuit breaking capacityxxxxxxx xxxxxxxx xxxxxxxx, 1s 40 kA Three0x 00 xX Xxxxx-phase xxxxx short-circuit breaking capacity 104kApeak The reactor circuit breakers shall comply with Standard IEEE Std.C37.015 regarding current opening and closing requirements.