Common use of DESCRIPTION OF SUPPLY Clause in Contracts

DESCRIPTION OF SUPPLY. F1.1. The Project shall be nominally 20 MW plus or minus five percent at 69 kV, 50 Hz from [name and location of project] and shall be comprised of the following equipment: F1.1.1. One (1) main 25 MVA, OA step-up transformer, wye 13.8/69 kV delta vector grouping, with provisions for grounding. Specification to meet standard ANSI BIL rating, with on-load tap changing capability of plus 5 to minus 10 percent. The on-load tap changer should be 1.25% for each step. F1.1.2. If used, two (2) 69 kV SF6 interrupting device (circuit breaker). The circuit breaker shall be rated for 52 kV, 3 cycle interrupt time, minimum 30 kA interrupting rating 1200 A continuous current rating, 350 kV BIL. F1.1.3. Metering equipment to include PT's, CT's, stands, and KWH/KVAR, KVA/KW meter type as required by Utility.

Appears in 4 contracts